Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
See Legend and Notes onpage10.
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph,60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
020
208/230 187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0
1
/
4
1.5
——
5.0 16.7/15.2
—— — 89/ 88 110/110 100/ 90
2 1.0 5.9 101/ 99 110/110 110/110
7.5 24.2/22.0
—— — 97/ 94 110/110 100/100
2 1.0 5.9 109/106 125/125 125/110
19/25 52/ 60
5.0 16.7/15.2
—— — 92/100 110/110 100/ 90
2 1.0 5.9 107/115 110/125 110/110
7.5 24.2/22.0
—— — 102/109 110/110 100/100
2 1.0 5.9 116/124 125/125 125/110
38/50 104/120
5.0 16.7/15.2
—— — 157/145 175/150 150/175
2 1.0 5.9 172/160 175/175 175/175
7.5 24.2/22.0
—— — 167/154 175/175 150/175
2 1.0 5.9 181/169 200/175 175/200
56/75 156/180
5.0 16.7/15.2
—— — 89/ 88 110/110 100/ 90
2 1.0 5.9 101/ 99 110/110 110/110
7.5 24.2/22.0
—— — 97/ 94 110/110 100/100
2 1.0 5.9 109/106 125/125 125/110
460 414 506 9.0 70.0 9.0 70.0 10.7 90.0 4.0
1
/
4
0.7
——
5.0 7.6
—— — 45 50 45
21.03.1 51 60 60
7.5 11.0
—— — 48 50 50
21.03.1 54 60 60
25 30
5.0 7.6
—— — 51 60 45
21.03.1 59 60 60
7.5 11.0
—— — 55 60 50
21.03.1 63 70 60
50 60
5.0 7.6
—— — 73 80 80
21.03.1 81 90 90
7.5 11.0
—— — 78 80 90
21.03.1 85 90 90
75 90
5.0 7.6
—— — 103 125 125
2 1.0 3.1 111 125 125
7.5 11.0
—— — 108 125 125
2 1.0 3.1 115 125 125
575 518 633 7.0 55.0 7.0 55.0 9.3 73.0 4.0
1
/
4
0.7
——
5.0 6.1
—— — 38 45 40
21.03.1 44 50 45
7.5 9.0
—— — 40 45 45
21.03.1 47 50 50
25 24
5.0 6.1
—— — 41 45 40
21.03.1 49 50 45
7.5 9.0
—— — 45 45 45
21.03.1 53 60 50
48 46
5.0 6.1
—— — 69 70 60
21.03.1 77 80 70
7.5 9.0
—— — 73 80 70
21.03.1 80 90 80
78 75
5.0 6.1
—— — 86 100 100
2 1.0 3.1 94 100 110
7.5 9.0
—— — 90 100 100
2 1.0 3.1 98 100 110
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
020 208/240 187 253 NA NA NA NA NA NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200 200/225
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
020 208/230 187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0
1
/
4
1.5 56/75 156/180
5.0 16.7/15.2
—— —183/205 200/225 200/225
2 1.0 5.9 198/220 200/225 225/250
7.5 24.2/22.0
—— —193/214 200/225 225/250
2 1.0 5.9 207/229 225/250 225/250