Carrier 50HG014-028 Air Conditioner User Manual


 
19
Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
See Legend and Notes onpage10.
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
028
208/230 187 253 47.1 245.0 47.1 245.0 ——6.0
1
/
4
1.5
——
7.5 24.2/22.0
—— — 144/142 175/175 150/150
2 1.0 5.9 156/154 200/200 175/175
10.0 30.8/28.0
—— — 151/148 175/175 175/175
2 1.0 5.9 163/160 200/200 175/175
19/25 52/ 60
7.5 24.2/22.0
—— — 144/142 175/175 150/150
2 1.0 5.9 156/154 200/200 175/175
10.0 30.8/28.0
—— — 151/148 175/175 175/175
2 1.0 5.9 163/160 200/200 175/175
38/50 104/120
7.5 24.2/22.0
—— — 167/154 175/175 150/175
2 1.0 5.9 181/169 200/200 175/200
10.0 30.8/28.0
—— — 175/161 175/175 175/175
2 1.0 5.9 190/176 200/200 175/200
56/75 156/180
7.5 24.2/22.0
—— — 144/142 175/175 150/150
2 1.0 5.9 156/154 200/200 175/175
10.0 30.8/28.0
—— — 151/148 175/175 175/175
2 1.0 5.9 163/160 200/200 175/175
460 414 506 19.6 125.0 19.6 125.0 ——6.0
1
/
4
0.7
——
7.5 11.0
—— — 62 80 70
21.03.1 69 80 70
10.0 14.0
—— — 65 80 70
21.03.1 72 90 80
25 30
7.5 11.0
—— — 62 80 70
21.03.1 69 80 70
10.0 14.0
—— — 65 80 70
21.03.1 72 90 80
50 60
7.5 11.0
—— — 78 80 90
21.03.1 85 90 90
10.0 14.0
—— — 81 90 90
2 1.0 3.1 89 100 100
75 90
7.5 11.0
—— — 108 125 125
2 1.0 3.1 115 125 125
10.0 14.0
—— — 111 125 125
2 1.0 3.1 119 125 150
575 518 633 15.8 100.0 15.8 100.0 ——6.0
1
/
4
0.7
——
7.5 9.0
—— — 52 60 60
21.03.1 58 70 60
10.0 11.0
—— — 54 60 60
21.03.1 60 70 70
25 24
7.5 9.0
—— — 52 60 60
21.03.1 58 70 60
10.0 11.0
—— — 54 60 60
21.03.1 60 70 70
48 46
7.5 9.0
—— — 73 80 70
21.03.1 80 90 80
10.0 11.0
—— — 75 80 70
21.03.1 83 90 80
78 75
7.5 9.0
—— — 90 100 100
2 1.0 3.1 98 100 110
10.0 11.0
—— — 93 100 100
2 1.0 3.1 100 110 110
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
028 208/240 187 253 NA NA NA NA NA NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200 200/225
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
028 208/230 187 253 47.1 245.0 47.1 245.0 ——6.0
1
/
4
1.5 56/75 156/180
7.5 24.2/22.0
—— —193/214 200/225 225/250
2 1.0 5.9 207/229 225/250 225/250
10.0 30.8/28.0
—— —201/221 225/225 225/250
2 1.0 5.9 216/236 225/250 250/300