Table 2A Electrical Data (Units Without Optional Convenience Outlet) (cont)
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
See Legend and Notes onpage10.
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
028
208/230 187 253 47.1 245.0 47.1 245.0 ——6.0
1
/
4
1.5
——
7.5 24.2/22.0
—— — 139/137 175/175 150/150
2 1.0 5.9 151/149 175/175 175/175
10.0 30.8/28.0
—— — 146/143 175/175 175/175
2 1.0 5.9 158/155 200/200 175/175
19/25 52/ 60
7.5 24.2/22.0
—— — 139/137 175/175 150/150
2 1.0 5.9 151/149 175/175 175/175
10.0 30.8/28.0
—— — 146/143 175/175 175/175
2 1.0 5.9 158/155 200/200 175/175
38/50 104/120
7.5 24.2/22.0
—— — 160/148 175/175 150/175
2 1.0 5.9 175/162 200/175 175/200
10.0 30.8/28.0
—— — 169/155 175/175 175/175
2 1.0 5.9 183/170 200/200 175/200
56/75 156/180
7.5 24.2/22.0
—— — 139/137 175/175 150/150
2 1.0 5.9 151/149 175/175 175/175
10.0 30.8/28.0
—— — 146/143 175/175 175/175
2 1.0 5.9 158/155 200/200 175/175
460 414 506 19.6 125.0 19.6 125.0 ——6.0
1
/
4
0.7
——
7.5 11.0
—— — 59 70 70
21.03.1 66 80 70
10.0 14.0
—— — 62 80 70
21.03.1 69 80 80
25 30
7.5 11.0
—— — 59 70 70
21.03.1 66 80 70
10.0 14.0
—— — 62 80 70
21.03.1 69 80 80
50 60
7.5 11.0
—— — 74 80 90
21.03.1 82 90 90
10.0 14.0
—— — 78 90 90
21.03.1 85 90 100
75 90
7.5 11.0
—— — 104 125 125
2 1.0 3.1 112 125 125
10.0 14.0
—— — 108 125 125
2 1.0 3.1 115 125 150
575 518 633 15.8 100.0 15.8 100.0 ——6.0
1
/
4
0.7
——
7.5 9.0
—— — 49 60 60
21.03.1 55 70 60
10.0 11.0
—— — 51 60 60
21.03.1 57 70 70
25 24
7.5 9.0
—— — 49 60 60
21.03.1 55 70 60
10.0 11.0
—— — 51 60 60
21.03.1 57 70 70
48 46
7.5 9.0
—— — 69 70 70
21.03.1 77 80 80
10.0 11.0
—— — 71 80 70
21.03.1 79 80 80
78 75
7.5 9.0
—— — 86 100 100
2 1.0 3.1 94 100 110
10.0 11.0
—— — 89 100 100
2 1.0 3.1 97 100 110
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3Ph, 60Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No.1 No.2 No.3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
028 208/240 187 253 NA NA NA NA NA NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200 200/225
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
028 208/230 187 253 47.1 245.0 47.1 245.0 ——6.0
1
/
4
1.5 56/75 156/180
7.5 24.2/22.0
—— —186/208 200/225 225/250
2 1.0 5.9 201/222 225/225 225/250
10.0 30.8/28.0
—— —195/215 225/225 225/250
2 1.0 5.9 209/230 225/250 250/300