MAXIMUM SHIPPING WEIGHT
Lb Kg
2535 1150
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductworktobeattached toaccessoryroofcurbonly.
5. Minimum clearance:
a. Rear: 7Ј0Љ (2134) for coil removal. This dimen-
sion can be reduced to 4Ј0Љ (1219) if conditions
permit coil removal from the top.
b. 4Ј0Љ(1219) tocombustiblesurfaces,allfour sides
(includes between units).
c. Left side: 4Ј0Љ (1219) for proper condenser coil
airflow.
d. Front: 4Ј0Љ (1219) for control box access.
e. Right side: 4Ј0Љ (1219) for proper operation of
damper and power exhaust (if so equipped).
f. Top: 6Ј0Љ (1829) to assure proper condenserfan
operation.
g. Bottom:14Љ(356) tocombustible surfaces(when
not using curb).
h. Control box side: 3Ј0Љ (914) to ungrounded sur-
faces (non-combustible).
i. Controlboxside:3Ј6Љ (1067)to blockorconcrete
walls, or other grounded surfaces.
j. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser
coilandthe damper/powerexhaustasstatedinNote
No. 5, a removable fence or barricade requires no
clearance.
7. Dimensions are from outside of corner post. Allow
0Ј-
5
⁄
16
Љ (8) on each side for top cover drip edge.
CORNER WEIGHT*
ABCD
Lb Kg Lb Kg Lb Kg Lb Kg
523 237 541 245 574 260 596 270
*Weights are for unit only and do not include options or crating.
Fig. 5 — Base Unit Dimensions, 48HJ025