Carrier 48HJ015-025 Heating System User Manual


 
UNIT
48HJ
MAXIMUM SHIPPING WEIGHT
Lb Kg
D015 1920 871
E015 1940 880
E017 2310 1048
UNIT
48HJ
DIMENSIONS
XY
Ft-in. mm Ft-in. mm
D015 3-2 965 4-0 1219
E015 3-2 965 4-0 1219
E017 3-7
3
8
1102 3-6
5
8
1083
UNIT
48HJ
WEIGHT OF CORNER*
ABCD
Lb Kg Lb Kg Lb Kg Lb Kg
D015 365 166 360 163 373 169 540 245
E015 372 169 363 165 377 171 547 248
E017 509 231 506 230 475 216 519 235
*Weights are for unit only and do not include options or crating.
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:
a. Rear:7Ј-0Љ(2134) forcoil removal.Thisdimensioncan bereduced
to 4Ј-0Љ (1219) if conditions permit coil removal from the top.
b. Left side: 4Ј-0Љ (1219) for proper condenser coil airflow.
c. Front: 4Ј-0Љ (1219) for control box access.
d. Right side: 4Ј-0Љ (1219) for proper operation of damper and power
exhaust (if so equipped).
e. Top: 6Ј-0Љ (1829) to assure proper condenser fan operation.
f. Local codes or jurisdiction may prevail.
6. Withtheexceptionofclearancefor thecondensercoilandthe damper/
power exhaust as stated in Note No. 5, a removable fence or barri-
cade requires no clearance.
7. Dimensions arefrom outside of corner post.Allow 0Ј-
5
16
Љ (8) on each
side for top cover drip edge.
Fig. 4 Base Unit Dimensions, 48HJ015,017