ACCESSORY
PACKAGE NO.
CURB
HEIGHT
DESCRIPTION ‘‘A’’ ‘‘B’’ ‘‘C’’
50PQ900221
1Ј-2Љ
(305)
Standard Curb —
14Љ High
———
50PQ900141
2Ј-0Љ
(610)
Standard Curb
for Units Requiring
High Installation
———
50PQ900151
2Ј-0Љ
(610)
Horizontal Supply
and Return Curb
5Ј-6Љ
(1676)
0Ј-2
1
⁄
2
Љ
(64)
1Ј-6Љ
(457)
50DP900211
1Ј-11Љ
(584)
Pre-Assembled,
High-Static,
Horizontal Adapter
6Ј-2Љ
(1880)
0Ј-6
1
⁄
4
Љ
(159)
1Ј-2
5
⁄
8
Љ
(371)
LEGEND
COMP SECT. — Compressor Section
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels,
1
⁄
2
-in. thick neoprene-coated, 2 lb density.
3. Dimensions in ( ) are in millimeters.
4. Direction of airflow.
5. Roof curb: 18 gage steel.
6. Attach all ductwork to roof curb.
7. Field installation of sidewall is mandatory.
NOTE: To prevent the hazard of stagnant water build-up in the drain
pan of the indoor-air section, unit can only be pitched as shown.
Fig. 1 — Roof Curb and Horizontal Adapter Details
2