Table 1H Electrical Data (COBRA Energy Recovery 50HJ008-014 Units with 62AQ300) (cont)
LEGEND
*Used to determine minimum disconnect per NEC.
Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
UNIT
NOMINAL
V-PH-Hz
IFM
TYPE
CONV
OUTLET
62AQ
FLA
HEATER
CRHEATER
---A00
HEAT POWER SUPPLY SINGLE
POINT BOX
CRSINGLE
---A00
DISCONNECT SIZE*
FLA MCA
FUSE OR
HACR BKR
MOCP FLA LRA
50HJ012
208/230-3-60
STD NO 29.8
NONE / 82.8/ 82.8 90/ 90 90/ 90 519/519
017 21.7/ 25.0 82.8/ 82.8 90/ 90 90/ 90 519/519
010 33.4/ 38.5 86.4/ 92.8 100/110 90/ 91 519/519
012 66.7/ 77.0 128.1/140.9 150/150 123/135 519/519
012+017 88.4/102.0 155.2/172.2 175/175 148/164 519/519
010+012 104.2/120.3 175.0/165.0 175/200 166/185 519/519
STD YES 29.8
NONE / 88.8/ 88.8 100/100 96/ 96 523/523
017 21.7/ 25.0 88.8/ 88.8 100/100 96/ 96 523/523
010 33.4/ 38.5 91.2/ 97.0 110/110 96/ 96 523/523
012 66.7/ 77.0 132.9/145.1 150/150 129/140 523/523
012+017 88.4/102.0 160.0/176.4 175/200 154/169 523/523
010+012 104.2/120.3 179.8/169.2 200/200 172/190 523/523
HIGH STATIC NO 29.8
NONE / 87.2/ 87.2 100/100 95/ 95 542/542
017 21.7/ 25.0 87.2/ 87.2 100/100 95/ 95 542/542
010 33.4/3 8.5 90.8/ 97.2 100/110 95/ 96 542/542
012 66.7/ 77.0 132.5/145.3 150/150 128/140 542/542
012+017 88.4/102.0 159.6/176.6 175/200 153/169 542/542
010+012 104.2/120.3 179.4/169.4 200/200 171/190 542/542
HIGH STATIC YES 29.8
NONE / 93.2/ 93.2 100/100 101/101 547/547
017 21.7/ 25.0 93.2/ 93.2 100/100 101/101 547/547
010 33.4/ 38.5 95.6/101.4 110/110 101/101 547/547
012 66.7/ 77.0 137.3/149.5 150/150 134/145 547/547
012+017 88.4/102.0 164.4/180.8 175/200 159/174 547/547
010+012 104.2/120.3 184.2/173.6 200/200 177/195 547/547
460-3-60
STD NO 15.8
NONE 40.7 45.0 ——44.0 260.0
016 16.7 45.8 60.0 011 44.0 261.0
013 19.8 49.7 60.0 011 47.0 261.0
014 33.4 66.7 80.0 014 62.0 261.0
014+016 50.2 87.6 100.0 016 81.0 261.0
013+015 60.1 85.0 110.0 016 93.0 261.0
STD YES 15.8
NONE 43.4 45.0 ——47.0 262.0
016 16.7 47.9 60.0 014 47.0 263.0
013 19.8 51.8 60.0 011 49.0 263.0
014 33.4 68.8 80.0 014 65.0 263.0
014+016 50.2 89.7 100.0 016 84.0 263.0
013+015 60.1 87.1 110.0 016 95.0 263.0
HIGH STATIC NO 15.8
NONE 43.3 50.0 ——47.0 272.0
016 16.7 48.4 60.0 014 47.0 272.0
013 19.8 52.3 60.0 011 50.0 272.0
014 33.4 69.3 80.0 014 65.0 272.0
014+016 50.2 90.2 100.0 016 84.0 272.0
013+015 60.1 87.6 110.0 016 96.0 272.0
HIGH STATIC YES 15.8
NONE 46.0 50.0 0.0 50.0 274.0
016 16.7 50.5 60.0 014 50.0 274.0
013 19.8 54.4 60.0 011 52.0 274.0
014 33.4 71.4 90.0 014 68.0 274.0
014+016 50.2 92.3 100.0 016 87.0 274.0
013+015 60.1 89.7 110.0 016 98.0 274.0
50HJ014
208/230-3-60
STD NO 29.8
NONE / 90.4/ 90.4 100/100 98/ 98 604/604
017 21.7/ 25.0 90.4/ 90.4 100/100 98/ 98 604/604
010 33.4/ 38.5 90.8/ 97.2 100/110 98/ 98 604/604
012 66.7/ 77.0 132.5/145.3 150/150 128/140 604/604
012+017 88.4/102.0 159.6/176.6 175/200 153/169 604/604
010+012 104.2/120.3 179.4/169.4 200/200 171/190 604/604
STD YES 29.8
NONE / 96.4/ 96.4 100/100 104/104 609/609
017 21.7/ 25.0 96.4/ 96.4 100/100 104/104 609/609
010 33.4/ 38.5 95.6/101.4 110/110 104/104 609/609
012 66.7/ 77.0 137.3/149.5 150/150 134/145 609/609
012+017 88.4/102.0 164.4/180.8 175/200 159/174 609/609
010+012 104.2/120.3 184.2/173.6 200/200 177/195 609/609
STD NO 15.8
NONE 44.9 50.0 ——49.0 287.0
016 16.7 48.4 60.0 014 49.0 287.0
013 19.8 52.3 60.0 011 50.0 287.0
016 16.7 48.4 70.0 014 49.0 287.0
014+016 50.2 90.2 100.0 016 84.0 287.0
013+015 60.1 87.6 110.0 016 96.0 287.0
STD
YES
15.8
NONE 47.6 50.0 ——51.0 289.0
016 16.7 50.5 60.0 014 51.0 289.0
013 19.8 54.4 60.0 011 52.0 289.0
016 16.7 50.5 70.0 014 51.0 289.0
014+016 50.2 92.3 100.0 016 87.0 289.0
013+015 60.1 89.7 110.0 016 98.0 289.0
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
UL
Underwriters Laboratories
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
7
457