Carrier 48/50HJ004-014 Indoor Furnishings User Manual


 
25
Table 1H Electrical Data (COBRA Energy Recovery 50HJ008-014 Units with 62AQ300)
UNIT
NOMINAL
V-PH-Hz
IFM
TYPE
CONV
OUTLET
62AQ
FLA
HEATER
CRHEATER
---A00
HEAT POWER SUPPLY SINGLE
POINT BOX
CRSINGLE
---A00
DISCONNECT SIZE*
FLA MCA
FUSE OR
HACR BKR
MOCP FLA LRA
50HJ008
208/230-3-60
STD NO 29.8
NONE / 68.0/ 68.0 80/80 ——75/ 75 420/420
017 21.7/ 25.0 68.7/ 72.9 90/ 90 007 75/ 75 420/420
010 33.4/ 38.5 83.3/ 89.7 100/100 007 81/ 87 420/420
011 51.7/ 59.7 106.2/116.2 125/125 009 102/112 420/420
012 66.7/ 77.0 125.0/137.8 150/150 009 120/131 420/420
012+017 88.4/102.0 152.1/169.1 175/175 009 145/160 420/420
STD YES 29.8
NONE / 74.0/ 74.0 80/80 ——80/ 80 425/425
017 21.7/ 25.0 74.0/ 77.1 90/ 90 007 80/ 80 425/425
010 33.4/ 38.5 88.1/ 93.9 100/110 009 87/ 92 425/425
011 51.7/ 59.7 111.0/120.4 125/125 009 108/116 425/425
012 66.7/ 77.0 129.8/142.0 150/150 009 125/136 425/425
012+017 88.4/102.0 156.9/173.3 175/175 009 150/165 425/425
HIGH STATIC NO 29.8
NONE / 71.1/ 71.1 80/80 ——78/ 78 445/445
017 21.7/ 25.0 71.8/ 76.0 90/ 90 007 78/ 78 445/445
010 33.4/ 38.5 86.4/ 92.8 100/110 009 85/ 91 445/445
011 51.7/ 59.7 109.3/119.3 125/125 009 106/115 445/445
012 66.7/ 77.0 128.1/140.9 150/150 009 123/135 445/445
012+017 88.4/102.0 155.2/172.2 175/175 009 148/164 445/445
HIGH STATIC YES 29.8
NONE / 77.1/ 77.1 80/80 ——84/ 84 449/449
017 21.7/ 25.0 77.1/ 80.2 90/100 007 84/ 84 449/449
010 33.4/ 38.5 91.2/ 97.0 110/110 009 90/ 96 449/449
011 51.7/ 59.7 114.1/123.5 125/150 009 111/120 449/449
012 66.7/ 77.0 132.9/145.1 150/150 009 129/140 449/449
012+017 88.4/102.0 160.0/176.4 175/200 009 154/169 449/449
460-3-60
STD NO 15.8
NONE 35.0 40.0 ——38.0 211.0
016 16.7 44.4 60.0 006 41.0 211.0
013 19.8 48.3 60.0 006 45.0 211.0
014 33.4 65.3 80.0 008 61.0 211.0
015 39.7 73.1 90.0 008 68.0 211.0
014+016 50.2 86.2 100.0 010 80.0 211.0
STD YES 15.8
NONE 37.7 40.0 ——41.0 213.0
016 16.7 46.5 60.0 006 44.0 213.0
013 19.8 50.4 60.0 006 47.0 213.0
014 33.4 67.4 80.0 008 63.0 213.0
015 39.7 75.2 90.0 008 70.0 213.0
014+016 50.2 88.3 100.0 010 82.0 213.0
HIGH STATIC NO 15.8
NONE 36.4 40.0 ——40.0 223.0
016 16.7 45.8 60.0 006 43.0 224.0
013 19.8 49.7 60.0 006 47.0 224.0
014 33.4 66.7 80.0 008 62.0 224.0
015 39.7 74.5 90.0 008 69.0 224.0
014+016 50.2 87.6 100.0 010 81.0 224.0
HIGH STATIC YES 15.8
NONE 39.1 45.0 ——43.0 225.0
016 16.7 47.9 60.0 006 45.0 226.0
013 19.8 51.8 60.0 006 49.0 226.0
014 33.4 68.8 80.0 008 65.0 226.0
015 39.7 76.6 90.0 008 72.0 226.0
014+016 50.2 89.7 100.0 010 84.0 226.0
50HJ009
208/230-3-60
STD NO 29.8
NONE / 70.0/ 70.0 80/80 —†77/ 77 454/454
017 21.7/ 25.0 70.0/ 72.9 90/ 90 012 77/ 77 454/454
010 33.4/ 38.5 83.3/ 89.7 100/100 012 81/ 87 454/454
011 51.7/ 59.7 106.2/116.2 125/125 015 102/112 454/454
012 66.7/ 77.0 125.0/137.8 150/150 015 120/131 454/454
012+017 88.4/102.0 152.1/169.1 175/175 015 145/160 454/454
STD YES 29.8
NONE / 76.0/ 76.0 80/80 —†82/ 82 459/459
017 21.7/ 25.0 76.0/ 77.1 90/ 90 012 82/ 82 459/459
010 33.4/ 38.5 88.1/ 93.9 100/110 015 87/ 92 459/459
011 51.7/ 59.7 111.0/120.4 125/125 015 108/116 459/459
012 66.7/ 77.0 129.8/142.0 150/150 015 125/136 459/459
012+017 88.4/102.0 156.9/173.3 175/175 015 150/165 459/459
HIGH STATIC NO 29.8
NONE / 73.1/ 73.1 80/80 —†80/ 80 479/479
017 21.7/ 25.0 73.1/ 76.0 90/ 90 012 80/ 80 479/479
010 33.4/ 38.5 86.4/ 92.8 100/110 015 85/ 91 479/479
011 51.7/ 59.7 109.3/119.3 125/125 015 106/115 479/479
012 66.7/ 77.0 128.1/140.9 150/150 015 123/135 479/479
012+017 88.4/102.0 155.2/172.2 175/175 015 148/164 479/479
HIGH STATIC YES 29.8
NONE / 79.1/ 79.1 80/80 —†86/ 86 483/483
017 21.7/ 25.0 79.1/ 80.2 90/100 012 86/ 86 483/483
010 33.4/ 38.5 91.2/ 97.0 110/110 015 90/ 96 483/483
011 51.7/ 59.7 114.1/123.5 125/150 015 111/120 483/483
012 66.7/ 77.0 132.9/145.1 150/150 015 129/140 483/483
012+017 88.4/102.0 160.0/176.4 175/200 015 154/169 483/483
460-3-60
STD NO 15.8
NONE 37.3 40.0 ——41.0 233.0
016 16.7 44.4 60.0 011 41.0 233.0
013 19.8 48.3 60.0 011 45.0 233.0
014 33.4 65.3 80.0 014 61.0 233.0
015 39.7 73.1 90.0 014 68.0 233.0
014+016 50.2 86.2 100.0 016 80.0 233.0
STD
YES
15.8
NONE 40.0 45.0 ——43.0 235.0
016 16.7 46.5 60.0 011 44.0 235.0
013 19.8 50.4 60.0 011 47.0 235.0
014 33.4 67.4 80.0 014 63.0 235.0
015 39.7 75.2 90.0 014 70.0 235.0
014+016 50.2 88.3 100.0 016 82.0 235.0
HIGH STATIC NO 15.8
NONE 38.7 45.0 ——42.0 245.0
016 16.7 45.8 60.0 011 43.0 246.0
013 19.8 49.7 60.0 011 47.0 246.0
014 33.4 66.7 80.0 014 62.0 246.0
015 39.7 74.5 90.0 014 69.0 246.0
014+016 50.2 87.6 100.0 016 81.0 246.0
HIGH STATIC
YES
15.8
NONE 41.4 45.0 ——45.0 247.0
016 16.7 47.9 60.0 011 45.0 248.0
013 19.8 51.8 60.0 011 49.0 248.0
014 33.4 68.8 80.0 014 65.0 248.0
015 39.7 76.6 90.0 014 72.0 248.0
014+016 50.2 89.7 100.0 016 84.0 248.0