The 42BHC and 42BVC fan coil units are designed to
offer maximum flexibility in an application, accessibility for
service, quiet operation and durability.
Factory-installed options
Automatic air vents — Automatic air vents have fiber-
washers, which allow air in the pipes to pass through,
automatically bleeding the system. The fiber washers elimi-
nate the need to manually remove air from the system.
When wet, washers swell and seal the system.
Coils — Coils are available in a choice of two-pipe system
with 4-row cooling/heating or four-pipe system with 4, 6
or 8-row cooling and 1 or 2 row heating.
Reheat operation is standard. Preheat is available as an
option.
Controls
Interlocking disconnect switch
Heater power fusing
24 v Class 2 transformer (40 va)
8-pole control terminal strip
Auto reset temperature limit switch
Airflow safety switch
Motor power fusing
Motor control contactor
24 v condensate overflow switch
Electric heat — Total electric heat eliminates the require-
ment for a boiler. Heating and/or cooling may be available
on an individual basis throughout the year. Resistance
electric heat is available from 1.0 kW to 40.0 kW (refer to
electric heater data table for availability per unit) with
single-stage or multiple-stage, single power source.
Voltages:
115 v, 208 v, 230 v and 277 v single-phase 60 Hz
208 v, 230 v and 480 v three-phase 60 Hz
Electric heat is available with the following staging options
(3-phase staging is balanced).
1 to 12 kW 1 stage only — single phase
3 to 12 kW 1 or 2 stage only — single phase
1 to 40 kW 1 stage only — 3 phase
4 to 40 kW 1 or 2 stage only — 3 phase
12 to 40 kW 1, 2, or 3 stage — 3 phase
Heater coils are constructed of high-grade resistance
wire that is supported by ceramic insulators on plated steel
brackets. These heat elements are suspended directly in
front of the outlet after the blower and the coil. High limit
thermal cutouts protect the heater in the event of air
failure.
Filters — Two in. pleated filters are standard. One-in.
pleated, two 1-in. throwaway, or 2-in. MERV (minimum
efficiency reporting value) 11 filters with 2-in. pleated
pre-filter are available. The 2-in. MERV 11 filters with 2-in.
pleated pre-filter include a filter rack.
Insulation — Tuf-Skin™ II (1-in. thick) insulation is
standard. Units are available with ¾-in. closed cell, 1-in.
Tuf-Skin Rx™ edge sealed, or 1-in. foil-faced insulation.
Motors — A wide selection of standard motors provides
efficient operation in ducted applications with excellent
performance with up to 2 inches of total static pressure.
Available motor options:
115 v, 208 v, 230 v and 277 v single-phase 60 Hz
208 v, 230 v and 460 v three-phase 60 Hz
Open drip-proof motors
External junction box
Field-installed accessories
Mixing boxes — Mixing boxes can be used when outside
air is required for ventilation. Preassembled at the factory
and shipped separately with base rails for field installation,
mixing boxes include a linkage kit consisting of two crank
arms, 2 swivels and either a 25 in. long (for sizes 06-16) or
a 84 in. long (for sizes 20-40) rod for field installation of an
actuator.
ITEM OPTION* ACCESSORY†
Automatic Air Vents X
Controls X
Electric Heat X
Filters X
Heating/Cooling Coils X
Insulation X
Mixing Boxes X
Motors X
Thermostats X
Valve Packages X
Options and accessories