Carrier 33ZCSECTRM Air Conditioner User Manual


 
33
Alarm Routing Control
This decision indicates which
CCN system software or devices will receive and process
alarms sent by the zone controller. This decision consists of
eight digits each can be set to zero or one. A setting of 1 indi-
cates alarms should be sent to this device. A setting of zero dis-
ables alarm processing for that device. Currently the corre-
sponding digits are configured for the following devices: first
digit - user interface software; second digit - autodial gateway
or Telink; fourth digit - alarm printer interface module; digits 3,
and 5 through 8 - unused.
Alarm Routing
Control: Range 00000000 to 11111111
Default Value 00000000
Re-Alarm Time
This decision is used to configure the num-
ber of minutes the zone controller will wait before an alarm
condition which has not been corrected will be re-transmitted
on the communications network. Re-alarming of an alarm con-
dition will continue until the condition no longer exists.
Alarm Re-Alarm
Time: Units Minutes
Range 0 to 1440
Default Value 0 (Disabled)
Space Temperature Occupied Hysteresis
This configura-
tion defines the range above the occupied high set point and be-
low the occupied low set point that the space temperature must
exceed for an alarm condition to exist during occupied hours.
Space Temperature
Occupied
Hysteresis: Units delta F (delta C)
Range 0.0 to 99.9
Default Value 5.0
Unoccupied Space Temperature Low Limit
This configu-
ration defines the lowest temperature that the unoccupied space
can be before an alarm is generated.
Unoccupied Space
Temperature
Low Limit: Units F (C)
Range 0 to 255 F
Default Value 40
Unoccupied Space Temperature High Limit
This configu-
ration defines the highest temperature that the unoccupied
space can be before an alarm is generated.
Unoccupied Space
Temperature
High Limit: Units F (C)
Range 0 to 255 F
Default Value 99
Occupied Humidity Low Limit
This configuration defines
the lowest humidity that the occupied space can be before an
alarm is generated.
Occupied Humidity
Low Limit: Units % humidity
Range 0 to 100%
Default Value 10
Occupied Humidity High Limit
This configuration de-
fines the highest humidity that the occupied space can be be-
fore an alarm is generated.
Occupied Humidity
High Limit: Units % humidity
Range 0 to 100%
Default Value 99
Unoccupied Humidity Low Limit
This configuration de-
fines the lowest humidity that the unoccupied space can be
before an alarm is generated.
Unoccupied
Humidity Low
Limit: Units % humidity
Range 0 to 100%
Default Value 0
Unoccupied Humidity High Limit
This configuration de-
fines the highest humidity that the unoccupied space can be
before an alarm is genenerated.
Unoccupied
Humidity High
Limit: Units % humidity
Range 0 to 100%
Default Value 100
Indoor Air Quality Low Limit
This configuration defines
the lowest CO
2
level that the occupied space can have before
an alarm is generated.
Indoor Air Quality
Low Limit: Units PPM (implied)
Range 0 to 5000
Default Value 250
Indoor Air Quality High Limit
This configuration defines
the highest CO
2
level that the occupied space can have before
an alarm is generated.
Indoor Air Quality
High Limit: Units PPM
Range 0 to 5000 PPM
Default Value 1200
High Velocity Pressure
This configuration defines the
maximum velocity pressure the zone controller should see at
the pickup mounted in the inlet of the terminal. This is also
used by the zone controller to calculate the maximum CFM the
terminal will be able to control to using the terminal inlet size
configured in the service configuration table.
High Velocity
Pressure: Units in. wg
Range 0.0 to 2.0 in. wg
Default Value 1.2
CONTROLLER IDENTIFICATION SCREEN The con-
troller identification screen displays the device information for
the zone controller.
HOLIDAY CONFIGURATION SCREENS The zone
controller has configuration screens for up to 12 different holi-
day schedules. Highlight the holiday name on the screen and
press enter to configure the holiday schedule. A separate screen
is used to ENTER the Holiday schedule.
Start Month
The start month is the month in which the hol-
iday starts. Months are represented by numbers with 1 repre-
senting January, 2 February, up to 12.
Start Month: Range 1 to 12
Default Value 1
Start Day
The start day is the day on which the holiday will
start.
Start Day: Range 1 to 31
Default Value 1
Duration
Length of time, in days, that the holiday will last.
Duration: Range 0 to 365
Default Value 0