Bryant SYSTXBBUIZ01 Thermostat User Manual


 
NORMAL airflow adjustment is used during dehumidifying. If
duct sweating is an issue, selecting HIGH will increase the
dehumidifying airflow and reduce the sweating.
LOW HEAT RISE:
ON
OFF (default)
Set this to ON if the system contains a bypass humidifier. The ON
setting will increase the furnace low heat airflow.
STAGING:
SYSTEM (default)
LOW
HIGH
Controls the staging of the furnace. SYSTEM setting will allow
the Evolution Zone Controlto determine furnace staging. LOW
will only run the low stage of furnace heat. HIGH will only run the
high stage of furnace heat.
OFF DELAY:
90 seconds
120 seconds (default)
150 seconds
180 seconds
Amount of time the blower will continue to run after heating has
shut off.
LOCKOUT TEMP:
NONE (default)
+5 to 55 deg F
Appears on dual fuel systems only (furnace with heat pump).
Outside temperature above which the furnace will NOT run.
Setup = FAN COIL:
HP/AC AIRFLOW:
EFFICIENCY
COMFORT (default)
MAXIMUM
Selects the airflow of the fan coil when heating or cooling with a
heat pump (or cooling with an AC unit). COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY is the airflow used to meet specified ratings. MAXI-
MUM is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.
DEHUM AIRFLOW:
NORMAL (default)
HIGH
Normal airflow adjustment used during dehumidifying. If duct
sweating is an issue, selecting HIGH will increase the dehumidi-
fying airflow speed and reduce the sweating.
HEATER SIZE:
(choices dependent upon fan coil model)
This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model
number of the fan coil). If the electric heater is self-identifying,
this value is not shown.
Setup = HEAT PUMP / AC:
COOLING LOCKOUT:
NONE (default)
45° F.
50° F.
55° F.
Outside temperature below which cooling will not be provided.
ENTERED SIZE:
(dependent on indoor unit model)
Size of the outdoor unit entered during the start-up process. If the
outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the
indoor unit can handle.
DEFROST INTERVAL:
30 minutes
60 minutes
90 minutes
120 minutes (default)
Time interval at which defrost cycles can occur on a heat pump.
ELECT HEAT LOCKOUT / LOCKOUT TEMP:
NONE (default)
+5 to 55 deg. F
Outside temperature above which the electric heat will not operate.
In dual fuel applications, heat pump will not operate below
selected temperature.
HIGH COOL LATCH:
NONE (default)
80 - 110 deg F
Outside temperature above which only the high speed (of a
2-speed outdoor unit) will run when cooling.
Setup = ZONING
DISABLE ZONING
No (default)
Yes
If Yes is selected, zoning is disabled and all dampers open. The
system will run unzoned using the Zone 1 sensor.
ZONE OFFSETS:
Zone Temperature Offsets (defaults = 0) Range -5° to +5°
This option allows actual temperature offset for each zone,
allowing calibration (or deliberate mis-calibration) of each sensor.
AIRFLOW LIMITS:
Low
Medium
High (default)
Maximum
Zone airflow limit, which is selectable for each zone. Low,
Medium, and High allows a relative noise/airflow relationship in a
zone (i.e. comfort vs. noise). Maximum allows unlimited
noise/airflow (i.e. maximum airflow allowed).
Setup = ACCESSORIES
FILTER TYPE:
MEDIA (i.e. TrueSense)
EAC
MEDIA+EAC (i.e. TrueSense)
CLEAN INTERVAL: 30 to 180 days (of actual blower operation).
(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies
to EAC filter selection only.
HUMIDIFIER INSTALLED:
NO
YES
If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months of humidifier
operation (default=6 months)