PERFORMANCE DATA (cont)
EVAPORATOR-FAN MOTOR PERFORMANCE
UNIT
EVAPORATOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
580D036
Standard
208/230
0.34 440
2.9
460 1.4
575 1.4
Alternate
208/230
1.00 1000
5.4
460 2.3
575 2.3
580D048
Standard
208/230
0.75 850
3.5
460 1.8
575 1.8
Alternate
208/230
1.00 1000
5.4
460 2.3
575 2.3
580D060
Standard
208/230
1.20 1340
5.9
460 3.2
575 3.2
Alternate
208/230
1.80 1921
8.9
460 4.7
575 4.7
580D072 Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
580D090 Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
580D102 Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
580D120
Standard
208/230
2.40 2120
6.1
460 2.7
575 2.7
Alternate
208/230
2.90 2615
7.9
460 3.6
575 3.6
580D150
Standard
208/230
4.20 3775
11.1
460 5.0
575 5.0
Alternate
208/230
5.25 4400
15.0
460 7.4
575 7.4
579F180 Standard
208/230
4.25 3775
10.5
460 4.8
579F216 Standard
208/230
5.90 5180
15.8
460 7.9
579F240 Standard
208/230 8.70 7915 22.0
460 9.50 8640 13.0
579F300 Standard
208/230 10.20 9510 28.0
460 11.80 11,000 14.6
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.