PERFORMANCE DATA (cont)
FAN PERFORMANCE 580D036-150 VERTICAL DISCHARGE UNITS
580D036 (3 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
Low Speed High Speed
208 V 230, 460, 575 V 208 V 230, 460, 575 V
Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts
900 0.49 0.21 253 0.50 0.23 277 0.51 0.26 307 0.55 0.31 363
1000 0.42 0.23 270 0.43 0.25 292 0.43 0.27 321 0.51 0.32 374
1100 0.37 0.24 287 0.38 0.26 307 0.39 0.28 335 0.46 0.33 385
1200 0.33 0.26 304 0.33 0.27 323 0.34 0.29 349 0.40 0.34 397
1300 0.27 0.27 321 0.28 0.29 338 0.28 0.31 364 0.34 0.34 408
1400 0.20 0.29 338 0.23 0.30 354 0.25 0.32 378
1500 0.16 0.30 355 0.18 0.31 369 0.20 0.33 392
LEGEND
Bhp Brake Horsepower Input to Fan
Esp External Static Pressure (in. wg)
FIOP Factory-Installed Option
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
page 52 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the
full range of the motor can be utilized with confidence. Using your fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
See Evaporator-Fan Motor Performance table on page 55 for addi-
tional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
580D036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
Airflow
Cfm
External Static Pressure (in. wg)
0.1 0.2 0.3 0.4 0.5 0.6
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
900 581 0.12 119 673 0.18 179 736 0.22 219 805 0.25 249 865 0.29 288 911 0.34 338
1000 644 0.19 189 709 0.22 219 782 0.28 279 835 0.30 298 900 0.35 348 937 0.38 378
1100 687 0.22 219 746 0.26 259 806 0.30 298 867 0.35 348 929 0.40 398 964 0.40 398
1200 733 0.26 259 785 0.32 318 843 0.35 348 903 0.41 408 960 0.47 467 994 0.50 497
1300 754 0.29 288 826 0.38 378 891 0.43 428 942 0.48 477 991 0.53 527 1047 0.60 597
1400 810 0.35 348 868 0.45 448 937 0.51 507 984 0.57 567 1032 0.62 617 1067 0.67 666
1500 841 0.42 418 911 0.53 527 985 0.61 607 1029 0.66 656 1073 0.72 716 1109 0.77 766
580D036 (3 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
Airflow
Cfm
External Static Pressure (in. wg)
0.7 0.8 0.9 1.0 1.1 1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
900 957 0.39 388 988 0.43 428 1039 0.47 448 1061 0.51 487 1083 0.54 527 1105 0.58 567
1000 992 0.44 438 1039 0.49 487 1061 0.55 507 1088 0.60 547 1111 0.66 587 1136 0.72 627
1100 1013 0.49 487 1068 0.55 547 1091 0.61 577 1109 0.66 607 1127 0.73 637 1145 0.80 666
1200 1045 0.56 557 1090 0.64 637 1109 0.68 647 1156 0.73 676 1203 0.81 706 1250 0.86 736
1300 1075 0.64 637 1122 0.70 696 1152 0.76 716 1190 0.82 756 1228 0.87 796 1266 0.94 836
1400 1110 0.73 726 1160 0.78 766 1181 0.83 806 1237 0.88 845 1293 0.94 885 1349 0.99 925
1500 1150 0.78 816 1190 0.84 855 1225 0.89 895 1271 0.95 945 1317 1.00 995 1383 1.05 1044
LEGEND
Bhp Brake Horsepower Input to Fan
FIOP Factory-Installed Option
Watts Input Watts to Motor
*Motor drive range is 760 to 1000 rpm. All other rpms require a field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See
page 52 for accessory/FIOP static pressure information.
3. Maximum continuous bhp is 1.0 and the maximum continuous watts
are 1000. Extensive motor and electrical testing on these units en-
sures that the full range of the motor can be utilized with confidence.
Using your fan motors up to the wattage ratings shown will not result
in nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 55 for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
5. Interpolation is permissible. Do not extrapolate.