PERFORMANCE DATA (cont)
FAN PERFORMANCE — 579F180-300 UNITS (cont)
579F216 (18 TONS)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
5000 669 1.10 1019 772 1.40 1291 870 1.80 1582 963 2.10 1903 1052 2.50 2251 1137 2.90 2623
5500 717 1.40 1292 813 1.80 1585 905 2.10 1892 992 2.50 2223 1076 2.90 2680 1157 3.30 2962
6000 767 1.80 1617 858 2.20 1932 944 2.50 2256 1026 2.90 2600 1104 3.30 2967 1181 3.80 3358
6500 817 2.20 1992 903 2.60 2329 985 3.00 2673 1062 3.40 3031 1136 3.80 3410 1209 4.30 3811
7000 869 2.70 2427 950 3.10 2787 1028 3.50 3151 1102 3.90 3527 1172 4.40 3919 1241 4.80 4331
7200 889 2.94 2624 969 3.34 2993 1046 3.74 3366 1118 4.18 3749 1187 4.64 4147 1255 5.08 4564
7500 920 3.30 2919 998 3.70 3303 1073 4.10 3689 1143 4.60 4083 1210 5.00 4490 1275 5.50 4914
8000 973 3.90 3476 1047 4.30 3886 1119 4.80 4294 1186 5.30 4708 1250 5.70 5131 — — —
8500 1026 4.60 4102 1097 5.10 4635 1166 5.60 4967 — — — — — — — — —
9000 1079 5.40 4800 — — — — — — — — — — — — — — —
579F216 (18 TONS)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.3 1.4 1.6 1.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
5000 1178 3.15 2820 1218 3.40 3016 1295 3.80 3425 1369 4.30 3849
5500 1196 3.55 3164 1234 3.80 3366 1309 4.20 3789 1381 4.70 4229
6000 1218 4.00 3565 1251 4.20 3772 1327 4.70 4206 1396 5.20 4658
6500 1244 4.50 4022 1279 4.70 4233 1348 5.20 4677 1415 5.80 5139
7000 1275 5.05 4547 1308 5.30 4762 — — — — — —
7200 1288 5.33 4783 — — — — — — — — —
7500 1307 5.75 5135 — — — — — — — — —
8000 —— — —— — —— — —— —
8500 —— — —— — —— — —— —
9000 —— — —— — —— — —— —
LEGEND
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
*Standard low-medium static drive range is 817 to 1038 rpm. Alternate
high static high static motor drive range is 994 to 1197. Other rpms re-
quire a field-supplied drive.
NOTES:
1. Static pressure losses (i.e., economizer) must be added to exter-
nal static pressure before entering Fan Performance table. See
Accessory/FIOP Static Pressure table on page 52 for more
information.
2. Interpolation is permissible. Do not extrapolate.
3. Maximum continuous bhp is 5.9 and the maximum continuous watts
are 5180. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized with con-
fidence. Using your fan motors up to the watts rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
4. Deduct 0.2 in. wg static pressure for high heat units at or above
8000 cfm.
48