Bryant 580D Heating System User Manual


 
PERFORMANCE DATA (cont)
FAN PERFORMANCE 580D036-150 VERTICAL DISCHARGE UNITS (cont)
580D072 (6 TONS)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.1 0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800 942 0.70 646 978 0.66 700 1063 0.82 771 1147 0.97 891 1248 1.20 1081 1322 1.33 1190
1900 982 0.80 739 1023 0.78 779 1097 0.91 843 1175 1.11 1006 1266 1.29 1156 1356 1.47 1310
2000 1022 0.91 835 1068 0.90 867 1132 1.01 924 1218 1.23 1106 1303 1.41 1258 1397 1.52 1353
2100 1063 0.99 916 1115 1.00 998 1180 1.17 1056 1261 1.35 1207 1340 1.53 1361 1428 1.66 1473
2200 1104 1.13 1039 1159 1.15 1081 1214 1.28 1148 1310 1.52 1353 1375 1.63 1447 1459 1.80 1595
2300 1130 1.26 1156 1202 1.29 1140 1248 1.38 1233 1358 1.69 1499 1410 1.72 1526 1488 1.93 1709
2400 1174 1.37 1258 1237 1.41 1224 1292 1.55 1378 1392 1.81 1604 1460 1.90 1683 1532 2.14 1892
2500 1201 1.48 1361 1272 1.53 1335 1335 1.71 1517 1427 1.94 1718 1518 2.16 1910 1575 2.35 2076
2600 1246 1.62 1491 1320 1.68 1482 1368 1.81 1604 1458 2.06 1823 1562 2.42 2136 1620 2.59 2283
2700 1285 1.75 1613 1361 1.82 1595 1400 1.91 1691 1490 2.19 1936 1602 2.64 2326 1666 2.85 2504
2800 1304 1.87 1726 1402 1.95 1639 1439 2.08 1840 1543 2.43 2145 1642 2.86 2512 —— —
2900 1345 2.07 1910 1446 2.16 1814 1477 2.16 1989 1585 2.65 2335 —— — —— —
3000 1378 2.26 2084 1489 2.36 2032 1529 2.52 2223 1598 2.73 2444 —— — —— —
580D072 (6 TONS)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2 1.4 1.6
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800 1395 1.46 1301 1475 1.56 1387 1542 1.71 1517
1900 1430 1.58 1404 1504 1.69 1499 1556 1.82 1613
2000 1459 1.67 1482 1532 1.82 1613 1588 1.97 1744
2100 1489 1.80 1595 1567 1.99 1761 1626 2.16 1910
2200 1528 1.95 1726 1603 2.17 1919 1666 2.37 2093
2300 1561 2.13 1884 1637 2.35 2076 1710 2.54 2272
2400 1584 2.28 2015 1671 2.55 2249 1756 2.70 2467
2500 1633 2.53 2232 1698 2.72 2405 —— —
2600 1675 2.77 2436 —— — —— —
2700 —— — —— — —— —
2800 —— — —— — —— —
2900 —— — —— — —— —
3000 —— — —— — —— —
LEGEND
Bhp Brake Horsepower Input to Fan
FIOP Factory-Installed Option
Watts Input Watts to Motor
*Motor drive range is 1070 to 1460 rpm. All other rpms require a field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See
page 52 for accessory/FIOP static pressure information.
3. Maximum continuous bhp is 2.40 and the maximum continuous
watts are 2120. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Evaporator-Fan Motor Performance
table on page 55 for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
5. Interpolation is permissible. Do not extrapolate.