Table 9 — Evaporator Fan Motor Data
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using fan motors up to the horsepower ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
GENERAL FAN PERFORMANCE NOTES
1. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
For additional information on motor performance refer to Table 9.
2. Values include losses for filters, unit casing, and wet coils. See
Table 8 for accessory/FIOP static pressure drop information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
UNIT
558F
EVAPORATOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM ACCEPTABLE
OPERATING WATTS
MAXIMUM
AMP DRAW
090,091
Standard,
Alternate
208/230
2.40 2120
6.7
460 3.0
575 3.0
High Static
208/230
3.70 3313
12.2
460 5.5
575 5.5
102,103
Standard
208/230
2.40 2120
6.7
460 3.0
575 3.0
High Static
208/230
3.70 3313
12.2
460 5.5
575 5.5
120,121
Standard
208/230
2.40 2120
6.7
460 3.0
575 3.0
Alternate
208/230
2.90 2615
8.6
460 3.9
575 3.9
High Static
208/230
5.25 4400
17.3
460 8.5
575 8.5
150,151
Standard
208/230
3.70 3313
12.2
460 5.5
575 5.5
Alternate
208/230
5.25 4400
17.3
460 8.5
575 8.5