Bradford-White Corp 55X80B*N Water Heater User Manual


 
Troubleshooting Chart
For Models Using Honeywell Gas Control
Observe LED indicator on gas control. Error flash codes
are displayed with a three second pause before repeating.
Check and repair the system as noted in the troubleshooting
table below:
LED Status Control Status Probable Cause
Not on and/or
not flashing
Pilot flame may not be present.
Gas control is in thePILOT” position and
the pilot flame is detected.
One flash and a three
second pause.
LED is on continuously
Gas control has recently been turned to the
“OFF” position. Wait until LED goes out
before attempting to relight.
Two flas hes and a three
second pause.
Weak pilot flame detected. System will reset
when pilot flame is sufficient.
Three flashes and a
three second pause.
Tank temperature fault.
System will reset.
Pilot flame is not present.
Gas control is powered and waiting for the set
point knob to be turned to a water
temperature setting.
Gas control was turned to the “OFF” position.
1. Thermopile failure
2. Unstable pilot.
3. Pilot tube blocked or restricted.
Thermowell sensor out of calibration.
Service
Procedure
1. Lite pilot per the instructions
located on the lighting
instructions label or the
lighting instructions located in
the installation and operation
manual.
2. See Service
Procedure AG-I,
Page 7.
Normal operation. Adjust gas
control set point knob to
desired temperature level.
1. Wait for LED to go out.
2. Lite pilot per the instructions
located on the lighting
instructions label or the
lighting instructions located in
the installation and operation
manual.
1. See Service
Procedure AG-I,
Page 7
2 & 3. See Service
Procedure AG-II,
Page 10.
1. See Service
Procedure AG-III,
Page 16
Four flashes and a three
second pause.
Excessive tank temperature. Thermowell sensor out of calibration.
1. See Service
Procedure AG-III,
Page 16
Page 4
LED Indicator
4