15
CF500/CF800 Burner Manual
Table 4 - Reset Button Operation
If the burner is in the
below state:
Pushing the reset button will:
Button Click
(press < 1 second)
Button Hold
(press > 1 second)
Button Hold
(press 15+ seconds)
Lockout Reset from Soft Lockout
Reset from Restricted
(Hard) Lockout
Valve-on Delay, Trial for
Ignition, Ignition Carryover
Go to Pump Prime (see
“Priming the Pump”
section in this manual.)
Disable the Burner:
Any time the burner
is running, press and
hold the reset button to
disable the burner. The
burner will remain off
as long as the button is
held.
Enables Pump Priming:
After the reset button
has been held for 15
seconds, the button
can then be clicked
during the next ignition
sequence to enter Pump
Prime mode.
Run (igniter is shut off) No action
Motor-Off Delay,
Standby
No action
Pump Prime No action Exit Pump Prime mode and return to Standby
Table 5 - Status Lights
Light Color On Continuously Flashing
Red Restricted (Hard) Lockout Soft Lockout
Green
Flame Sensed during normal operation
(Could be stray light during standby)
Recycle
Yellow
Control is in Pump Prime mode or
Reset button currently held for 15+ seconds.
N/A
Reset Button Operation
Table 4 explains what action the control will take when the reset button is pressed for different lengths of time during
the various burner operating states.
Section: Wire the Burner