Bard PA13302-A Air Conditioner User Manual


 
Manual 2100-467K
Page 21 of 24
TABLE 10
PRESSURE TABLE
LOW SIDE PRESSURE +4 PSIG
HIGH SIDE PRESSURE +10 PSIG
TablesbaseduponratedCFM(airow)acrosstheevaporatorcoil.
If incorrect charge suspected (more than +4psigsuction,+10psigliquid),
itisrecommendedrefrigerantchargebereclaimed,systemevacuatedandchargedtoserialplatequantity.
COOLING
Air Temperature Entering Outdoor Coil Degree F
Model
Return Air
Temperature
Pressure 65° 70° 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° 125°
PA1342
75° DB
62° WB
Low Side
High Side
126
242
128
265
129
288
131
311
132
334
134
357
136
380
137
409
138
437
140
466
141
494
142
523
143
551
80° DB
67° WB
Low Side
High Side
135
248
137
272
138
295
140
319
142
343
143
366
144
402
146
419
148
448
149
478
151
507
152
536
153
565
85° DB
72° WB
Low Side
High Side
145
257
147
281
149
306
151
330
152
355
154
379
156
404
157
434
159
464
160
494
162
525
163
555
165
585
PA1348
75° DB
62° WB
Low Side
High Side
125
239
127
263
128
287
129
311
130
335
132
359
133
383
134
410
136
438
137
465
139
492
140
520
142
547
80° DB
67° WB
Low Side
High Side
134
245
135
270
137
294
138
319
139
344
141
368
142
404
144
421
145
449
147
477
148
505
150
533
152
561
85° DB
72° WB
Low Side
High Side
144
254
145
279
147
305
148
330
150
356
151
381
153
407
154
436
156
465
158
494
160
523
161
552
163
581
PA1360
75° DB
62° WB
Low Side
High Side
124
224
125
254
126
285
127
315
128
345
129
375
130
406
131
431
131
456
132
480
133
505
134
530
80° DB
67° WB
Low Side
High Side
133
230
134
261
135
292
136
323
137
354
138
385
138
426
140
442
141
467
141
493
142
518
143
544
85° DB
72° WB
Low Side
High Side
143
238
144
270
145
302
146
334
147
366
148
398
149
431
150
457
151
484
152
510
153
537
154
563