40
PROBLEMS
NOT ENOUGH HOT WATER
1.)Blowerwillnotrun.
a.“ON/OFF”controlswitchturnedoff. Turnswitchtothe“ON”position.
b.Blowerunplugged. Plugblowerbackinto115VACoutlet.
c.Nopoweratoutlet. Repairservicetooutlet.
d.Thermostatdefective. Replacethermostat.
e. Control harness defective. Replacecontrolharness.
f.Highlimitcontrolcircuitopen.
Reducethewatertemperaturebelow140°F.
Turnthepowerswitchtotheoffposition.
Wait10seconds.Turnthepowerswitchto
theonposition.Reducethe
temperatureset
pointtominimizelikelihoodofreoccurrence.
If
thisdoesnotsolvetheproblem,replacethe
thermostat.
g.Blowermotordefective. Replaceblowerassembly.
2.)Thermostatproblems
a.Thermostatsettoolow. Adjusttemperaturecontrolhigher.
b.ThermostatorECOdefective Replacethermostat.
3.)Others
a.Heaterundersized.. Reduce hot water use.
b.Lowgaspressure Contact dealer.
c.Incomingwaterisusuallycold. Allowmoretimeforheatertoreheat.
d.Leakinghotwaterpipesoffixtures. Haveplumbercheckandrepairleaks.
e.Heaternotlitorthermostatnoton. Refer to LIGHTING INSTRUCTIONS.
VENT PIPE TOO HOT (ABOVE 170°F [77°C]) Wrongburnerorice. Turnoffheaterandgas,cleanburnerhead.
YELLOW FLAME
Dirtinburnerports. Turnoffheaterandgas,cleanburnerhead.
Combustionairpathrestricted.
Checkexhaustventingandairopenings
inbottombase pan for obstructionsor
blockage.
CONDENSATION Waterontheoorunderheater. See CONDENSATION section.
WATER LEAKS
Improperly sealed,hot orcoldsupply
connections, relief valve, drain valve or
thermostatthreads.
Checkforleaks.SeeFigure1.
Leakagefromotherappliancesorwaterlines.
Inspectotherappliancesnearwaterheater.
Condensationofueproducts. Refer to CONDENSATION section.
LEAKING T & P
Thermalexpansioninclosedwatersystem.
Installthermalexpansiontank(Donotplug
T&Pvalve).
Improperlysealedvalve.
Checkreliefvalveforproperoperation(Do
notplugT&Pvalve).
HOT WATER ODORS
(refer to cathodic protection)
Highsulfateormineralcontentinwater
supply.
Drainandushheaterthoroughlythenrell.
Bacteriainwatersupply. Chlorinatewatersupply.
HOT WATER TOO HOT Thermostatsettoohigh.
Refer to TEMPERATURE REGULATION
section.
WATER HEATER SOUNDS Condensationdrippingonburner. Refer to CONDENSATION above.
SIZZLING - RUMBLING Sedimentatbottomofheatertank.
Clean sediment from tank. Refer to
DRAINING.
SOOTING Impropercombustion. RefertoAirRequirements.
BURNER WILL NOT STAY LIT-GOES OUT
4-5 SECONDS
Outletpolarityisreversed. Testpolarityandcorrect.
Highambientroomtemperature.
Contact aqualified serviceagencyto
determinecause.
Defectivegascontrolvalvethermostat
. Replace
gascontrolvalvethermostat
.
VENT GAS ODORS
Lackofairsupply.
Shutoffwaterheaterimmediatelyandcontacta
qualiedserviceagencytodeterminecause.
Improperlyinstalledventpiping.
Downdraft
PoorCombustion
TROUBLESHOOTING GUIDELINES
Theseguidelinesshouldbeutilizedbyaqualiedserviceagent.