UW 2 Speed Pocket Hardmount
Electrical Specifications
Voltage Designation Standard Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Breaker
AWG
mm
2
Full Load
Amps
Breaker
AWG
mm
2
35
D 220-240 50 3 3 7 20 12 3x4 38 50 6 3x16
F* 440-480 60 3 3 5 15 14 3x2.5 25 30 10 3x6
G 440 50 3 3 5 15 14 3x2.5 25 30 10 3x6
H 380 60 3 3 5 15 14 3x2.5 20 25 10 3x6
M 550-575 60 3 3 5 15 14 3x2.5 Not available in this voltage.
O* 208-240 60 3 3 7 20 12 3x4 38 50 6 3x16
S 380 50 3 3 5 15 14 3x2.5 20 25 10 3x6
W 380-415 50 3 3 5 15 14 3x2.5 22 30 10 3x6
Y* 208-240 60 1 2 12 25 10 2x6 Not available in this voltage.
60
D 220-240 50 3 3 11 30 10 3x6 66 80 3 3x30
F* 440-480 60 3 3 7 25 10 3x6 33 40 8 3x10
G 440 50 3 3 7 25 10 3x6 30 40 8 3x10
H 380 60 3 3 7 25 10 3x6 26 35 8 3x10
M 550-575 60 3 3 7 25 10 3x6 Not available in this voltage.
O* 208-240 60 3 3 11 30 10 3x6 66 80 3 3x30
S 380 50 3 3 7 25 10 3x6 26 35 8 3x10
W 380-415 50 3 3 7 25 10 3x6 33 40 8 3x10
NOTE: Wire sizes shown are for copper, THHN, 90° conductor per NEC article 310.
Table 8