York YHJD18 thru 60 Heat Pump User Manual


 
571209-YTG-C-1012
6 Johnson Controls Unitary Products
MA Modular Air Handlers use Coil Only Ratings.
PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Ratings.
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT MODEL
COIL
CFM RANGE
(Min.-max.)
COOLING
MODEL WIDTH
RATED
CFM
NET MBH
SEER
1
EER
TOTAL SENS.
13 SEER HP COIL ONLY RATINGS
YHJD18S41S2
FC/MC/PC18 14.5,17.5 450 - 750 600 18.0 14.0 13.00 11.00
FC/MC/PC24 14.5,17.5 450 - 750 600 18.0 14.0 13.50 11.00
FC/MC/PC30 14.5,17.5 450 - 750 600 18.0 13.7 13.00 11.00
UC24 14.5,17.5 450 - 750 600 18.0 13.8 13.05 11.00
UC30 14.5,17.5 450 - 750 600 18.0 13.8 13.05 11.00
YHJD24S41S4
FC/MC/PC32 14.5 600 - 1000 800 23.8 17.1 13.00 11.00
FC/MC/PC35 17.5,21.0 600 - 1000 800 23.6 17.1 13.00 11.00
FC/MC/PC37 14.5 600 - 1000 800 24.0 17.3 13.00 11.00
FC/MC/PC43 17.5,21.0 600 - 1000 800 24.0 17.3 13.00 11.00
YHJD30S41S4
FC/MC/PC32 14.5 800 - 1200 1000 29.8 21.8 13.00 11.00
FC/MC/PC35 17.5,21.0 800 - 1200 1000 29.8 21.8 13.00 11.00
FC/MC/PC37 14.5 800 - 1200 1000 30.0 22.2 13.00 11.00
FC/MC/PC43 17.5,21.0 800 - 1200 1000 30.0 22.2 13.00 11.00
YHJD36S41S4
FC/MC/PC37 14.5 1000 - 1400 1200 36.0 26.8 13.00 11.00
FC/MC/PC43 17.5,21.0 1000 - 1400 1200 36.0 26.6 13.00 11.00
FC/MC/PC48 21.0,24.5 1000 - 1400 1200 36.0 26.6 13.00 11.00
UC48 21.0,24.5 1000 - 1400 1200 36.0 26.8 13.00 11.00
YHJD42S41S4
FC/MC/PC60 21.0,24.5 1200 - 1600 1400 41.0 31.8 13.00 11.00
UC60 21.0,24.5 1200 - 1600 1400 40.5 31.0 13.00 11.00
YHJD48S41S4
FC/MC/PC60 21.0,24.5 1400 - 1800 1600 44.0 33.4 13.00 11.00
FC/MC62 24.5 1400 - 1800 1600 44.5 33.8 13.00 11.00
UC60 21.0,24.5 1400 - 1800 1600 44.0 32.8 13.00 11.00
YHJD60S41S5
FC/MC62 24.5 1600 - 2000 1800 57.5 41.0 13.25 11.35
FC64 24.5 1600 - 2000 1800 56.5 42.5 13.00 11.00
1. Requires a S1-2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
COOLING CAPACITY - With High Efficiency Motor Furnaces
UNIT
MODEL
FURNACE
COIL
MODEL
1
COOLING
MODEL WIDTH
RATED
CFM
Net MBH
SEER EER
TOTAL SENS.
13 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES
2
YHJD18S41S2
T*(8,L)V*A12 14.5 FC/MC/PC18A 620 18.0 12.3 14.50 12.30
T*(8,L)V*A12 14.5 FC/MC/PC24A 640 18.0 12.7 14.80 12.50
T*(8,L)V*A12 14.5 FC/MC/PC30A 640 18.0 12.7 14.80 12.50
T*(8,L)V*A12 14.5 UC18A 620 18.0 12.4 14.60 12.30
T*(8,L)V*A12 14.5 UC24A 640 18.0 12.8 14.80 12.50
T*(8,L)V*A12 14.5 UC30A 640 18.0 12.8 14.80 12.50
T*(8,L)V*B12 14.5 FC/MC/PC18A 620 18.0 12.3 14.50 12.30
T*(8,L)V*B12 17.5 FC/MC/PC24B 575 18.0 12.2 14.90 12.60
T*(8,L)V*B12 17.5 FC/MC/PC30B 575 18.0 12.2 14.90 12.60
T*(8,L)V*B12 17.5 UC18B 580 18.0 12.0 14.60 12.30
T*(8,L)V*B12 17.5 UC24B 575 18.0 12.3 14.90 12.60
T*(8,L)V*B12 17.5 UC30B 575 18.0 12.3 15.00 12.60
T*(8,L)X*A12 14.5 FC/MC/PC18A 540 18.0 14.3 14.00 12.00
T*(8,L)X*A12 14.5 FC/MC/PC24A 595 18.0 14.9 14.00 12.00
T*(8,L)X*A12 14.5 FC/MC/PC30A 595 18.0 14.9 14.00 12.00
T*(8,L)X*A12 14.5 UC18B 590 18.0 13.9 14.50 12.00
For Notes See Page 12.