York YHJD18 thru 60 Heat Pump User Manual


 
571209-YTG-C-1012
28 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD30S41S4
INDOOR COIL MODEL NO. AHP30
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 800 1000 1200
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 29.1 31.3 31.4 34.3 36.1 31.0 32.7 32.8 35.2 36.6 33.0 34.1 34.1 36.1 37.2
S.C. 28.0 24.7 21.2 21.0 17.8 29.9 27.9 23.3 22.4 18.2 31.8 31.1 25.4 23.8 18.6
KW 2.00 2.00 2.00 2.10 2.00 2.10 2.10 2.10 2.10 2.10 2.20 2.20 2.20 2.20 2.20
75
T.C. 27.4 29.1 29.2 32.3 34.3 29.3 30.4 30.4 33.2 34.9 31.3 31.6 31.6 34.0 35.5
S.C. 26.4 23.7 20.2 20.1 16.8 28.3 26.5 22.3 21.7 17.4 30.2 29.3 24.4 23.3 18.0
KW 2.10 2.20 2.20 2.20 2.20 2.20 2.30 2.30 2.30 2.30 2.30 2.40 2.30 2.30 2.30
85
T.C. 25.7 26.9 27.0 30.3 32.5 27.6 28.0 28.0 31.1 33.2 29.6 29.1 29.1 31.9 33.9
S.C. 24.8 22.7 19.2 19.3 15.8 26.6 25.1 21.3 21.0 16.6 28.5 27.5 23.3 22.7 17.3
KW 2.20 2.30 2.30 2.30 2.40 2.40 2.40 2.40 2.40 2.50 2.50 2.50 2.50 2.50 2.50
95
T.C. 24.0 24.7 24.7 28.2 30.8 25.9 25.7 25.7 29.1 31.5 27.8 26.7 26.6 29.9 32.2
S.C. 23.1 21.8 18.2 18.4 14.8 25.0 23.7 20.2 20.3 15.8 26.8 25.7 22.3 22.1 16.7
KW 2.40 2.40 2.40 2.50 2.50 2.50 2.50 2.50 2.60 2.60 2.60 2.60 2.60 2.70 2.70
105
T.C. 21.8 22.2 21.8 25.3 28.3 23.6 23.5 22.6 26.1 29.0 25.4 24.8 23.4 26.9 29.7
S.C. 21.0 20.4 17.0 17.3 13.8 22.8 22.2 18.9 19.2 14.8 24.5 24.0 20.9 21.1 15.8
KW 2.50 2.50 2.50 2.60 2.70 2.70 2.70 2.60 2.70 2.80 2.80 2.80 2.70 2.80 2.90
115
T.C. 19.7 19.6 19.0 22.3 25.8 21.4 21.3 19.6 23.2 26.5 23.0 23.0 20.2 24.0 27.1
S.C. 19.0 18.9 15.8 16.1 12.7 20.6 20.6 17.6 18.0 13.8 22.2 22.2 19.5 20.0 14.9
KW 2.70 2.70 2.70 2.70 2.80 2.80 2.80 2.80 2.90 2.90 2.90 2.90 2.90 3.00 3.10
125
T.C. 17.5 17.1 16.1 19.4 23.4 19.1 19.1 16.5 20.3 24.0 20.7 21.2 16.9 21.1 24.6
S.C. 16.9 17.1 14.6 14.9 11.7 18.4 19.0 16.3 16.9 12.8 19.9 20.4 16.9 18.9 13.9
KW 2.80 2.80 2.80 2.90 2.90 2.90 2.90 2.90 3.00 3.10 3.10 3.10 3.00 3.10 3.30
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Air Handlers Coils T.C. S.C. KW
FC/MC/PC32 1.00 1.05 1.00
FC/MC/PC35 1.00 1.05 1.00
FC/MC/PC37 1.02 1.07 1.00
FC/MC/PC43 1.02 1.07 1.00
AHE30B 1.02 1.06 0.94
AHE36C 1.04 1.11 0.92
AHR30B 1.02 1.11 1.01
AHR36B 1.03 1.10 1.01
AHV30B 1.02 1.07 0.96
AHV36C 1.02 1.05 0.91
AV*36 1.04 1.09 0.91
MV12B FC/MC35B 1.02 1.07 0.92
MV12B FC/MC43B 1.04 1.09 0.93
MV16C FC/MC35C 1.04 1.12 0.92
MV16C FC/MC43C 1.04 1.09 0.93
MX12B FC/MC35B 1.03 1.12 0.93
MX12B FC/MC43B 1.05 1.15 0.94
MX16C FC/MC35C 1.03 1.08 0.90
MX16C FC/MC43C 1.05 1.10 0.91