York YCAL0080SC Heat Pump User Manual


 
YORK INTERNATIONAL
91
FORM 150.62-NM1
LOW AMBIENT CONDENSER FAN CONTROL
For unit operation below 25°F (-3.9°C) a low ambient
kit is required. The kit consists of a discharge pressure
transducer(s) and reversing contactors.
With the low ambient kit installed and the unit pro-
grammed for low ambient operation, the condenser fans
will operate as shown in Tables 41 and 42.
TABLE 41 LOW AMBIENT CONDENSER FAN CONTROL AMBIENT TEMPERATURE AND DISCHARGE
PRESSURE CONTROL
Again, notice that condenser fan operation can be pro-
grammed for either temperature and discharge pres-
sure control, or discharge pressure control only as
described under Condenser Fan Control.
The fan control on-pressure (ctrl_press) and the fan def-
erential off-pressure (diff_press) are programmable un-
der the PROGRAM key.
TABLE 42 LOW AMBIENT CONDENSER FAN CONTROL DISCHARGE PRESSURE CONTROL
2
FAN STAGE ON OFF
1
OAT >25° F (-3.9°C) OAT < 20° F (-6.7°C)
1 FAN REV
OR AND
DP > ctrl_press DP < ctrl_press - diff_press
2
OAT >45°F (7.2°C) OAT < 40°F (-4.40°C)
1 FAN FWD
OR AND
DP > ctrl_press + 20 PSIG (1.38 Bars) DP < ctrl_press - diff_press + 20 PSIG (1.38 Bars)
3
OAT > 65°F (18.3°C) OAT < 60°F (15.6°C)
2 FANS FWD
OR AND
DP > ctrl_press + 40 PSIG (2.76 Bars) DP < ctrl_press - diff_press + 40 PSIG (2.76 Bars)
FAN STAGE ON OFF
1
1 FAN REV DP > ctrl_press DP < ctrl_press - diff_press
2
1 FAN FWD DP > ctrl_press + 20 PSIG (1.38 Bars) DP < ctrl_press - diff_press + 20 PSIG (1.38 Bars)
3
2 FANS FWD DP > ctrl_press + 40 PSIG (2.76 Bars) DP < ctrl_press - diff_press + 40 PSIG (2.76 Bars)