York YCAL0080SC Heat Pump User Manual


 
YORK INTERNATIONAL
26
ELECTRICAL DATA OPTIONAL SINGLE POINT POWER
YCAL0040SC - YCAL0060SC
TABLE 5 OPTIONAL SINGLE POINT POWER
See notes and legend on pages 18 and 19.
SINGLE POINT FIELD SUPPLIED WIRING
MODEL
INCOMING WIRE RANGE
6
YCAL
VOLT HZ MCA
1
MIN N/F
D.E. FUSE CKT. BKR.
5
FACTORY SUPPLIED OPTIONAL
DISC SW
2
MIN
3
MAX
4
MIN MAX SINGLE POINT DISCONNECT BREAKER
0040SC
200 60 173 200 200 200 200 200 2/0 - 4/0 2/0 - 4/0 2/0 - 4/0
230 60 161 200 175 175 175 175 2/0 - 4/0 2/0 - 4/0 2/0 - 4/0
380 60 102 150 110 110 110 110 # 2 - 1/0 # 2 - 1/0 # 2 - 1/0
460 60 77 100 90 90 90 90 # 4 - # 1 # 4 - # 1 # 4 - # 1
575 60 62 100 70 70 70 70 # 6 - # 2 # 6 - # 2 # 6 - # 2
0044SC
200 60 247 400 300 300 300 300 250 - 350 250 - 350 250 - 350
230 60 229 250 250 250 250 250 4/0 - 300 4/0 - 300 4/0 - 300
380 60 139 200 150 150 150 150 1/0 - 3/0 1/0 - 3/0 1/0 - 3/0
460 60 110 150 125 125 125 125 # 2 - 1/0 # 2 - 1/0 # 2 - 1/0
575 60 88 100 100 100 100 100 # 2 - 1/0 # 2 - 1/0 # 2 - 1/0
0050SC
200 60 261 400 300 300 300 300 300 - 400 300 - 400 300 - 400
230 60 243 400 300 300 300 300 250 - 350 250 - 350 250 - 350
380 60 145 200 175 175 175 175 1/0 - 3/0 1/0 - 3/0 1/0 - 3/0
460 60 116 150 125 125 125 125 # 1 - 2/0 # 1 - 2/0 # 1 - 2/0
575 60 93 150 100 110 100 110 # 2 - 1/0 # 2 - 1/0 # 2 - 1/0
0060SC
200 60 267 400 300 300 300 300 300 - 400 300 - 400 300 - 400
230 60 248 400 300 300 300 300 250 - 350 250 - 350 250 - 350
380 60 145 200 175 175 175 175 1/0 - 3/0 1/0 - 3/0 1/0 - 3/0
460 60 119 150 125 125 125 125 # 1 - 2/0 # 1 - 2/0 # 1 - 2/0
575 60 95 150 100 110 100 110 # 2 - 1/0 # 2 - 1/0 # 2 - 1/0
Installation