York YCAL0080SC Heat Pump User Manual


 
YORK INTERNATIONAL
83
FORM 150.62-NM1
Condenser fans are controlled by ambient tempera-
t
ure and discharge pressure. This mode must be cho-
sen if the discharge pressure transducers are not in-
stalled, or if the fan cycling is a concern.
Option 11 Manual Override Mode
This option allows overriding of the daily schedule that
is programmed. MANUAL OVERRIDE MODE-DISABLED
indicates that override mode has no effect.
or
Manual Override Mode is enabled. This is a service func-
tion and when enabled, will allow the unit to start when
shut down on the daily schedule. It will automatically be
disabled after 30 minutes.
CLOCK
The CLOCK display shows the current day, time, and
date. Pressing the CLOCK key will show the current
day, time, and date.
It is important that the date and time be correct, other-
wise the daily schedule will not function as desired if
programmed. In addition, for ease of troubleshooting
via the History printouts, the day, time, and date should
be correct.
To change the day, time, and date press the CLOCK
key. The display will show something similar to the fol-
lowing:
The line under the F is the cursor. If the day is correct,
press the ENTER/ADV key. The cursor will move under
the 0 in 08 hours. If the day is incorrect, press the UP or
DOWN
arrow keys until the desired day is displayed
and then press the ENTER/ADV key at which time the
day will be accepted and the cursor will move under the
0. In a similar manner, the hour, minute, meridian, month,
day, and year may be programmed, whenever the cur-
sor is under the first letter/numeral of the item.
Jumper J11 on the microboard must
be set to the “CLKON” position to turn
on the clock. If this is not done the
clock will not function.
Option 8 Units Type
Display messages will show units of measure in
Imperial units (
°F or PSI
).
or
Display messages will show units of measure in SI
units (
°
C or Bar).
Option 9 Lead/Lag Type (two systems only)
SYS 1 selected as lead compressor.
or
SYS 2 selected as lead compressor.
or
In this mode the micro determines which system is as-
signed to the lead and lag. A new lead/lag assignment
is made whenever all compressors shut down. The mi-
cro will then assign the lead to the compressor with
the shortest average run time.
Option 10 Condensed Fan Control Mode
Condenser fans are controlled by discharge pressure
only. This mode may only be chosen when discharge
pressure transducers are installed, or if fan cycling is
not a concern.
or
DISPLAY UNITS
IMPERIAL
DISPLAY UNITS
SI
LEAD / LAG CONTROL
MANUAL SYS 1 LEAD
LEAD / LAG CONTROL
AUTOMAT I C
LEAD / LAG CONTROL
MANUAL SYS 2 LEAD
MANUAL OVERR I DE MODE
D I SABLED
FAN CONTROL
D I SCHARGE PRESSURE
FAN CONTROL
AMB I ENT & DSCH PRESS
MANUAL OVERR I DE MODE
ENABLED
TODAY I S FR I 08 : 51AM
1MAY98
2