York WR240 Air Conditioner User Manual


 
262292-YTG-B-0107
8 Unitary Products Group
FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS - Includes a slide-in / plug-in damper
assembly with fully modulating spring-return motor
actuator capable of introducing up to 100% outdoor air
with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
POWER EXHAUST - Our single economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood must be assembled
and installed in the field.
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and must
be field assembled before installing.
PHENOLIC COATED EVAPORATOR, REHEAT, AND
CONDENSER COILS - Special coating process that
utilizes Technicoat 10-1" processes. Coating is applied by
total immersion of the complete coil for maximum
protection.
ELECTRIC HEATERS wired for single point power
supply. These nickel chromium heater elements are
provided with limit and automatic reset capability to
prevent operation at excessive temperatures.
VARIABLE AIR VOLUME (VAV) - A factory-installed
variable frequency drive (VFD), mounted in the Blower
Access compartment, is used to control the speed of the
indoor blower motor in order to maintain a constant static
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box.
The drive comes completely wired and pre-programmed
from the factory.
An optional, factory-installed manual bypass switch avail-
able with factory-installed VFD can be found in the Blower
Motor Access compartment. The switch can be used to
either route power to the VFD for modulating control of the
blower motor, to bypass the drive and operate the motor
at full speed, or to power the drive (and not the motor) for
diagnostic purposes.
Due to space limitations, VAV is not available with any of
the factory-installed BAS options described below, but is
available with ‘BAS-ready’ models. Terminal blocks are
provided in the control box for field wiring of the customer-
installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus-
tomer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment which
may accommodate other vendor’s drives depending on
their size. In order to utilize the unit’s mounting bracket,
the maximum recommended drive dimensions are as fol-
lows:
For 5-hp motor applications ........................13” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D
If the customer-installed drive will not fit in the allotted
space, then it will have to be mounted within a NEMA-4
enclosure for outside installation or inside the building on
a perpendicular wall not subjected to excessive tempera-
ture, vibration, humidity, dust, corrosive gas, explosive
gas, etc.
A terminal block located in the control box is provided for
field connection of the VFD controls.
HOT GAS BYPASS - To allow for low cooling load opera-
tion, a direct-acting pressure-modulating bypass control
valve installed on the system #1 discharge line is used to
divert high temperature, high pressure refrigerant around
the TXV in order to maintain a desired minimum evaporator
pressure. HGBP is standard on all units with VAV and
optional with CV units.
FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated
filters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or you
may order the unit with a “non-powered” convenience
outlet that can be wired in the field.
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
DOUBLE WALL CONSTRUCTION - Optional double wall
construction is available to provide smooth inner surfaces
for easy and effective cleaning to reduce risk of dirt and
bacterial accumulation. Fiberglass insulation is
sandwiched between heavy gauge steel sheets to form a
durable, rigid casing to withstand higher working
pressures and impact forces. The heavy-duty construction
provides excellent acoustic and thermal insulation and
eliminates erosion of insulation material and
contamination of the air stream.
BAS - Building Automation System Controls
(available on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York®
Simplicity® INTELLI-Comfort™ control is factory installed.
It includes a supply air sensor, a return air sensor, and an
outside air sensor. There are provisions for a field installed
dirty filter indicator switch, an air-proving switch, an Out-
side Air Humidity sensor, a Return Air Humidity sensor, an
Inside IAQ sensor, and an Outside Air IAQ sensor. Con-