York WR240 Air Conditioner User Manual


 
262292-YTG-B-0107
Unitary Products Group 29
TABLE 14: WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW
Blower Performance (Downflow Discharge)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP
0.2
7541 1120 5.34 6.51 7285 1082 4.81 5.87 6996 1043 4.28 5.22 6716 1005 3.85 4.63 6406 966 3.40 4.08 6050 926 3.00 3.61
0.4
7197 1122 5.02 6.12 6947 1083 4.51 5.50 6655 1044 4.06 4.88 6367 1005 3.58 4.29 6034 966 3.08 3.70 5675 927 2.74 3.29
0.6
6854 1123 4.69 5.72 6616 1084 4.21 5.14 6347 1046 3.81 4.58 6066 1006 3.41 4.09 5738 967 3.06 3.67 5321 927 2.58 3.09
0.8 6576 1125 4.49 5.48 6348 1086 4.04 4.84 6072 1046 3.62 4.35 5747 1007 3.20 3.84 5325 968 2.78 3.33 4923 928 2.38 2.86
1.0
6287 1126 4.27 5.21 6069 1087 3.84 4.61 5686 1048 3.37 4.04 5340 1008 2.88 3.46 4917 969 2.54 3.05 4463 929 2.08 2.50
1.2
5911 1127 3.97 4.76 5707 1088 3.57 4.29 5310 1049 3.08 3.69 4911 1009 2.62 3.14 4463 970 2.25 2.70 3949 930 1.87 2.24
1.4
5545 1128 3.66 4.39 5354 1089 3.29 3.95 4896 1049 2.82 3.38 4458 1010 2.33 2.80 4038 970 1.96 2.36 3152 931 1.53 1.83
1.6
5209 1130 3.38 4.06 4941 1090 3.04 3.65 4391 1050 2.51 3.02 3924 1011 2.07 2.48 3158 971 1.64 1.97 - - - -
1.8
4638 1131 2.96 3.56 4314 1091 2.66 3.19 3681 1052 2.14 2.57-- ---- ------
1 turn 2 turns 3 turns 4 turns 5 turns 6 turns
7.5 HP motor 5 HP motor
15-Ton High Static Drive, Gas Heat, Bottom Connection
1VP62 x BK90
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
External Static ("WC)
SCFM
1 Turn
2 Turns
3 Turns
5 Turns
6 Turns
4 Turns