TABLE 4: COOLING CAPACITIES FOR WR180 (CONTINUED)
Air on Evaporator Coil
Temperature of Air on Condenser Coil
115°F 125°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
*
Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
3750
77 18715.87366503417 - 17917.37460473013 -
72 172 15.6 110 93 77 61 44 28 165 17.1 108 91 74 57 40 23
67 157 15.4 146 120 104 88 71 55 151 16.9 142 118 101 84 67 50
62 147 15.2
147 147 121 104 88 72 143 16.7 145 143 117 100 83 66
4500
77 19315.99274553618 - 18417.39270513213 -
72 177 15.7 122 103 84 66 47 29 169 17.1 119 100 81 62 43 24
67 162 15.5 151 133 114 95 77 58 155 16.9 146 130 111 92 73 54
62 152 15.2 151 151 133 114 96 77 147 16.7
147 146 128 109 90 71
57 151 15.2
151 151 136 117 99 80 146 16.6 146 146 130 111 92 73
5250
77 198 15.9 111 81 60 39 18 - 188 17.4 111 80 56 35 14 -
72 183 15.7 133 113 92 71 51 30 173 17.2 130 109 88 67 46 25
67 167 15.5 156 145 124 103 83 62 159 17.0 150 142 121 100 79 58
62 156 15.3
156 156 144 124 103 82 151 16.8 149 149 139 118 97 76
57 156 15.2
156 156 148 127 106 86 150 16.7 150 150 141 120 99 78
6000
77 204 16.0 130 88 65 42 19 - 193 17.4 130 90 60 37 14 -
72 188 15.8 145 122 99 77 54 31 177 17.2 142 118 95 72 49 26
67 172 15.6 160 157 134 111 88 66 162 17.0 153 147 131 108 84 61
62 161 15.4 160 160 156 133 110 87 154 16.8 153 153 151 127 104 81
57 160 15.3
160 160 160 137 114 91 154 16.7 154 154 153 130 107 84
6750
72 193 15.8 156 131 106 82 57 32 182 17.2 151 127 102 77 52 28
67 176 15.6 165 163 144 119 94 69 166 17.0 157 154 139 115 90 65
62 165 15.4
165 165 163 138 113 89 158 16.8 157 157 156 131 107 82
57 165 15.3
165 165 164 140 115 90 157 16.7 157 157 157 133 107 83
7500
72 198 15.8 167 140 113 87 60 34 186 17.1 161 135 108 82 55 29
67 181 15.6 169 169 153 126 100 73 170 16.9 161 161 148 122 95 69
62 169 15.3
169 169 169 143 116 90 162 16.7 161 161 161 135 109 82
57 169 15.2
169 169 169 143 116 89 161 16.6 161 161 161 136 108 82
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity