York WR240 Air Conditioner User Manual


 
262292-YTG-B-0107
Unitary Products Group 43
NOTE 1: HACR Type per NEC.
TABLE 30: WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET
MODEL
(TONNAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
AMPS
HEATER OPTION MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL KW STAGES AMPS
180
(15)
208 22.4 164 2.1 20.0 10.0
None - - - 88.8 110
E18 13.5 1 37.5 88.8 110
E36 27 2 74.9 131.2 150
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 187.7 200
230 22.4 164 2.1 20.0 10.0
None - - - 88.8 110
E18 18.0 1 43.3 91.6 110
E36 36.0 2 86.6 145.8 150
E54 54.0 2 129.9 167.4 175
E72 72.0 2 173.2 210.7 225
460 10.9 100 1.2 10.0 5.0
None - - - 44.3 50
E18 18.0 1 21.7 45.8 50
E36 36.0 2 43.3 72.9 80
E54 54.0 2 65.0 83.7 90
E72 72.0 2 86.6 105.4 110
575 8.3 78 0.9 7.5 4.0
None - - - 33.8 40
E18 18.0 1 17.3 36.0 40
E36 36.0 2 34.6 57.7 60
E54 54.0 2 52.0 66.3 70
E72 72.0 2 69.3 83.7 90
240
(20)
208 30.1 225 2.4 38.6 10.0
None - - - 128.1 150
E18 13.5 1 37.5 128.1 150
E36 27 2 74.9 154.4 175
E54 40.6 2 112.7 201.6 225
E72 54.1 2 150.2 210.9 225
230 30.1 225 2.4 38.6 10.0
None - - - 128.1 150
E18 18.0 1 43.3 128.1 150
E36 36.0 2 86.6 169.0 175
E54 54.0 2 129.9 190.7 225
E72 72.0 2 173.2 234.0 250
460 15.5 114 0.9 19.3 5.0
None - - - 63.7 80
E18 18.0 1 21.7 63.7 80
E36 36.0 2 43.3 84.5 90
E54 54.0 2 65.0 95.3 110
E72 72.0 2 86.6 117.0 125
575 12.1 80 0.6 16.2 4.0
None - - - 50.9 60
E18 18.0 1 17.3 50.9 60
E36 36.0 2 34.6 68.6 70
E54 54.0 2 52.0 77.2 90
E72 72.0 2 69.3 94.5 100
300
(25)
208 42.3 245 2.4 38.6 10.0
None - - - 153.4 175
E18 13.5 1 37.5 153.4 175
E36 27 2 74.9 154.4 175
E54 40.6 2 112.7 201.6 225
E72 54.1 2 150.2 210.9 225
230 42.3 245 2/4 38.6 10.0
None - - - 153.4 175
E18 18.0 1 43.3 153.4 175
E36 36.0 2 86.6 169.0 175
E54 54.0 2 129.9 190.7 225
E72 72.0 2 173.2 234.0 250
460 17.6 125 0.9 19.3 5.0
None - - - 67.9 80
E18 18.0 1 21.7 67.9 80
E36 36.0 2 43.3 84.5 90
E54 54.0 2 65.0 95.3 110
E72 72.0 2 86.6 117.0 125
575 14.5 100 0.6 16.2 4.0
None - - - 55.7 70
E18 18.0 1 17.3 55.7 70
E36 36.0 2 34.6 68.6 70
E54 54.0 2 52.0 77.2 90
E72 72.0 2 69.3 94.5 100
VOLTAGE LIMITATIONS ELECTRIC HEAT CORRECTION FACTORS
POWER SUPPLY
VOLTAGE NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
MIN. MAX. 208 208 1.00
VOLTAGE
LIMITATIONS
1
208/230-3-60 187 253 240 230 0.92
460-3-60 414 506 480 460 0.92
575-3-60 518 630 600 575 0.92
1. Utilization Range “A” in accordance with ARI Standard 110.