York DM 078 Air Conditioner User Manual


 
246645-YTG-C-0708
12 Johnson Controls Unitary Products
TABLE 3: DM CAPACITY RATINGS
Size
(Tons)
Model
Cooling Capacities
ARI Ratings
*
CFM
Sound
Rating
(dB)
Nominal
Electric Heat
Capacity
(kW)
Gas Heat Capacity
Gas Line
Size
(in. OD)
MBH EER IPLV
Input
(MBH)
Output
(MBH)
Seasonal
Efficiency
(%)
Temp.
Rise
(°F)
078
(6-1/2)
Cooling
Only
77 9.0 9.45 2600 84
------
Electric
Heat
9, 18, 24, 34 - - - - -
Gas Heat - 120 96 80 20-50 3/4
Gas Heat - 180 144 80 35-65 3/4
090
(7-1/2)
Cooling
Only
86 9.0 9.2 2886 89
------
Electric
Heat
18, 34 - - - - -
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
102
(8-1/2)
Cooling
Only
99 9.0 10.04 3400 90
------
Electric
Heat
9, 18, 24, 34 - - - - -
Gas Heat - 120 96 80 15-45 3/4
Gas Heat - 180 144 80 30-60 3/4
120
(10)
Cooling
Only
120 9.0 9.10 4000 90
------
Electric
Heat
9, 24, 34 54 - - - - -
Gas Heat - 180 144 80 20-50 3/4
Gas Heat - 240 192 80 35-65 3/4
150
(12-1/2)
Cooling
Only
144 9.3 9.25 4500 90
------
Electric
Heat
9, 24, 34, 54 - - - - -
Gas Heat - 180 144 80 10-40 3/4
Gas Heat - 240 192 80 25-55 3/4
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
Rated in accordance with ARI 270 standard.
See Table 20.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING MIN. MAX.
208/230-3-60
187 252
460-3-60
432 504
575-3-60
540 630