Weil-McLain GOLD DV WATER BOILER Boiler User Manual


 
95Part number 550-141-850/0699
Installation Start-Up Parts Maintenance
Table 11 Boiler dimensional data (see Figure 40)
Table 12 Boiler ratings
Boiler
model
Supply
(in. NPT)
Return
(in. NPT)
Length
L
(inches)
Gas
connection
size
(Note 1)
(in. NPT)
Crate dimensions
(outside measurement, inches)
Approx.
shipping
weight
(pounds)
Length Width Height
GV3 1 1 30¾ ½ 33½ 22 36 270
GV4 1 1 30¾ ½ 33½ 22 36 320
GV5 1 1 37¾ ½ 33½ 22 43 355
GV6 1 1 37¾ ½ 33½ 22 43 410
Note 1 Gas piping from meter to boiler to be sized per local utility requirements.
Boiler
model
number
AGA Input
Btuh
DOE Heating
capacity Btuh
(Note 1)
Net I=B=R
ratings Btuh
(Note 2)
DOE
Seasonal
efficiency (%)
Vent/combustion
air diameter
(inches)
Boiler water
content
(gallons)
GV-3 70,000 61,000 53,000 87.5 3
3.3
GV-4 105,000 92,000 80,000 87.3 3
4.2
GV-5 140,000 122,000 106,000 87.2 3 5.1
GV-6 175,000 153,000 133,000 87.0 3
6.0
Notes:
1. Based on standard test procedures prescribed by the United States Department of Energy. Ratings also referred to as AGA/
CGA Output.
2. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing
need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15. An additional
allowance should be made for unusual piping and pickup loads.
Boilers are tested for 50 lbs working pressure. GV boilers are not available for millivolt systems.