Weil-McLain GOLD DV WATER BOILER Boiler User Manual


 
Part number 550-141-850/069980
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manualGOLD GV Water boiler series 3 manual
GOLD GV Water boiler series 3 manual
CHART 7
LIMIT
light flashing and
POWER
light on steady
This is not a lockout mode. The control module should only be signaling that the water temperature sensor is either shorted or
there is an open circuit across the sensor terminals..
This situation is usually corrected by replacing the sensor, as described below.
Electrical shock hazard Wherever you see
TURN OFF POWER
, follow the instructions. Failure to follow
instructions could result in severe personl injury, death or substantial property damage.
Remove
SENSOR
plug from receptacle on GCM (
Figure 34, Item
6
). Then re-insert.
Does LIMIT light still flash?
No Yes
No Yes
Boiler may now be operating correctly. Verify per normal
sequnce of operation in Figure 22.
Replace sensor and harness.
Does LIMIT light still flash?
Replace GCM (control module).
Retest.
Troubleshooting GCM lights (continued)XIg