Trane TCONT802AS32DA Dehumidifier User Manual


 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
69-1790—3 14
Deadband 0310 2 thru 9 Heating and cooling
setpoints can be set
no closer than chosen
value:
2—2°F (1°C)
3—3°F (2°C)
4—4°F (2.5°C)
5—5°F (3°C)
6—6°F (3.5°C)
7—7°F (4°C)
8—8°F (4.5°C)
9—9°F (5°C)
3 Heating and cooling setpoints
can be set no closer than 3°F
(1.5°C).
Shown only if
automatic
changeover is
selected.
The deadband is
restricted to the range
of 5 to 9 if ISU 0380 is
set to
dehumidification
droop control.
Temperature
Indication
Scale
0320 0 Temperature is
displayed in °F.
1 Temperature is displayed in °C.
Daylight
Savings
0330 1 Daylight savings
enabled (use through
2006 and for areas
that do not
use the
new 2007 DST
calendar).
0, 2 0—daylight savings is
disabled.
2—daylight savings is enabled
(start using in 2007, for areas
that use the new 2007 DST
calendar).
Set to 0 in areas that
do not follow daylight
savings.
Remote
Temperature
Sensor
(Outdoor or
Indoor)
0340 0 No remote
temperature sensor
1-3 1—outdoor temperature
sensor for display only.
2—outdoor temperature
sensor for system control,
used for select heat pump
systems. (See Special Heat
Pump Features section for
more details.)
3—indoor temperature sensor
Defaults and Options
depend on System
Type selection.
Indoor Temperature
Sensor uses an
averaging network
and does not include
on-board sensor.
Heat Pump
Compressor
Lockout
0350 0 No compressor
lockout.
15, 20,
25, 30,
35, 40,
45
15°F (-9.5°C)
20°F (-6.5°C)
25°F (-4°C)
30°F (-1°C)
35°F (1.5°C)
40°F (4.5°C)
45°F (7°C)
Default depends on
other selections.
Shown if Outdoor
Temperature for
control is selected.
Heat Pump
Auxiliary
Lockout
0360 0 No heat pump
auxiliary lockout.
40, 45,
50, 55,
60
40°F (4.5°C)
45°F (7°C)
50°F (10°C)
55°F (13°C)
60°F (15.5°C
Shown if electric is
chosen for backup
heat source and
outdoor temperature
sensor for control is
selected.
Indoor
Dehumidifica-
tion Control
0380 0 No indoor
dehumidification
control.
1 1—dehumidification droop
control.
Available on models
with humidity sensor.
Furnace Filter
Change
Reminder
0500 0 Furnace filter change
reminder off.
1-6 1—10 run time days
2—30 run time days
3—60 run time days
4—90 run time days
5—120 run time days
6—365 run time days
Run time based on
call for fan.
Humidifier
Pad
Replacement
Reminder
0510 0 Humidifier pad
replacement reminder
off.
1-3 1—90 calendar days
2—180 calendar days
3—365 calendar days
Table 4. Installer Setup Menu. (Continued)
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description