Trane TCONT802AS32DA Dehumidifier User Manual


 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION
Pub. No. 18-HD25D19-3
69-1790—3 12
IMPORTANT
The Installer Setup Menu (Table 4) shows all the available options. These options customize themselves as
you make selections to the Installer Setup. Therefore, not all Installer Setup Selections are shown or are avail-
able to change.
Table 4. Installer Setup Menu.
Select
Installer
Setup
Number
Factory Setting Other Choices
CommentsOption Description Options Description
Not used. 1 thru
0099
—— —
Date (Year
Upper)
0120 20 Set first two digits of
current calendar year
(20 for year 2005, etc)
21 21 —first two digits of current
calendar year (21xx)
2000 - 2178 available
Date (Year
Lower)
0130 05 Represents last two
digits of current
calendar year (2005).
00 -99 Select last two digits of current
calendar year.
2000 - 2178 available
Date (Month) 0140 6 Digit(s) represents
current calendar
month.
1-12 Select number that represents
current calendar month.
Date
(Day)
0150 15 Digit(s) represents
current calendar date.
1-31 Select number that represents
current calendar date.
Schedule
Options
0160 4 7-day programming 0 0—nonprogrammable
System Type
Selection
0170 1 1 Heat/1Cool 1-12 1—1heat/1cool
2—single-stage heat pump (no
aux. heat)
3—heat only (no fan)
4—heat only (with fan)
5—hot water Series 20 (3-wire
or normally open zone valves)
6—cool only
7—2 heat/1cool heat pump
8—2 heat/2 cool
9—2 heat/1cool
10—1 heat/2 cool oil furnace
or 0H/2C
11—2 heat/2 cool heat pump
(with no auxiliary heat)
12—3 heat/2 cool heat pump
(with auxiliary heat)
Available options and
defaults vary by
comfort control.
System selection
automatically
modifies some
default settings and/
or hides other
Installer Setup
options.
Fan Operation 0180 0 Heat/Cool
applications where
equipment controls
fan operation in heat
mode.
1 Heat pump or electric heat
applications where comfort
control controls fan operation
in heat mode.
Only shown if heat/
cool system is
selected. If heat
pump is chosen, fan
defaults to electric.
Backup Heat
Source
(Auxiliary
Heat)
0200 0 Heat pump backup
heat source is electric.
1 Heat pump backup heat
source is fossil fuel.
Only shown if 2 heat/
1 cool or 3 heat/2
cool heat pump is
chosen.
External
Fossil Fuel Kit
0210 1 External fossil fuel kit
is controlling heat
pump backup heat
(recommended)
0 No external fossil fuel kit is
controlling heat pump backup
heat. This comfort control
controls the backup fossil fuel
heat with outdoor sensor.
Only shown if fossil
fuel is chosen as
backup heat source.
Cycles per
hour (cph) for
1st Stage
Compressor
0220 3 Compressor Stage 1
cycles per hour (cph)
1-6 1-6 available;
3 is recommended.
Cycles per
hour (cph) for
2nd Stage
Compressor
0230 3 Compressor Stage 2
cycles per hour (cph)
1-6 1-6 available;
3 is recommended.
Only shown if two
stages of cool are
selected.