Weights
Table W- 1 — Maximum Unit Weights, Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Unit Maximum Weights (Lbs) Corner Weights (Lbs)
1
Center of Gravity (In.)
Tons Model No. Shipping Net A B C D Length Width
3 WSC036A 534 442 138 110 88 105 31 19
4 WSC048A 566 474 151 114 95 114 31 19
5 WSC060A 584 492 160 118 97 117 31 19
6 WSC072A 867 724 243 184 128 170 38 22
WSC090A 937 794 272 200 137 185 38 22
10 WSC120A 1084 941 320 243 162 215 38 21
Note:
1. Corner weights are given for information only.
Table W-2 — Factory-installed Options Net Weights (Lbs)
1,2
Net Weight
Accessory 3-5 Tons 6-10 Tons
Economizer 26 36
Barometric Relief 7 10
Powered Exhaust 80
Motorized Outside Air Damper 20 30
Manual Outside Air Damper 16 26
Roof Curb 70 115
Oversized Motor 5 8
Belt Drive Motor 31
Smoke Detector, Return 7 7
Smoke Detector, Supply 5 5
Coil Guards 12 20
Hinged Doors 10 12
Powered Convenience Outlet 38 38
Through the Base Electrical 8 13
Electric Heaters 15 30
Unit Mounted Circuit Breaker 5 5
Unit Mounted Disconnect 5 5
Notes:
1. Weights for options not listed are < 5 lbs.