Trane PKGP-PRC003-EN Heat Pump User Manual


 
30
PKGP-PRC003-EN
Table PD-29 — 4 Ton Single Phase Heating Capacities (Net) WSC048A3,A4,AW At 1600 CFM
Outdoor Instantaneous Heating Capacity (Btuh/1000) Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp. at Indicated Indoor Dry Bulb Temp.
1
Indicated Indoor Dry Bulb Temp.
F 60 70758060 7075 8060707580
-8 17.4 17.0 16.8 16.6 15.7 15.3 15.1 14.9 3.61 3.99 4.22 4.48
-3 19.5 19.1 18.8 18.6 17.6 17.2 16.9 16.7 3.57 3.96 4.20 4.48
2 21.9 21.3 21.2 21.1 19.7 19.2 19.1 19.0 3.65 4.02 4.24 4.50
7 24.3 23.7 23.5 23.4 21.9 21.3 21.2 21.1 3.69 4.05 4.27 4.52
12 27.0 26.3 26.1 25.9 24.3 23.7 23.5 23.3 3.73 4.09 4.31 4.54
17 29.7 28.9 28.7 28.5 26.7 26.0 25.8 25.7 3.78 4.14 4.35 4.58
22 32.5 31.7 31.4 31.1 29.3 28.5 28.3 28.0 3.83 4.19 4.40 4.62
27 35.5 34.6 34.3 33.9 32.0 31.1 30.9 30.5 3.89 4.24 4.45 4.67
32 38.6 37.7 37.3 36.9 34.7 33.9 33.6 33.2 3.95 4.30 4.51 4.72
37 41.7 40.7 40.2 39.8 37.5 36.6 36.2 35.8 4.01 4.37 4.57 4.78
42 44.8 43.7 43.2 42.7 40.3 39.3 38.9 38.4 4.08 4.44 4.64 4.85
47 48.0 46.8 46.3 45.7 48.0 46.8 46.3 45.7 4.16 4.52 4.72 4.93
52 51.2 49.9 49.3 48.7 51.2 49.9 49.3 48.7 4.25 4.61 4.81 5.01
57 54.4 53.0 52.3 51.7 54.4 53.0 52.3 51.7 4.35 4.71 4.90 5.10
62 57.6 56.0 55.3 54.5 57.6 56.0 55.3 54.5 4.45 4.81 5.00 5.20
67 57.4 55.7 54.8 53.9 57.4 55.7 54.8 53.9 4.45 4.79 4.97 5.16
72 60.7 58.8 57.9 57.0 60.7 58.8 57.9 57.0 4.58 4.93 5.11 5.30
For other airflow conditions, see heating capacity correction factor (Table PD-39).
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.
Table PD-28 — 4Ton Three Phase Heating Capacities (Net) WSC048A1 At 1600 CFM
Outdoor Instantaneous Heating Capacity (Btuh/1000) Integrated Heating Capacity (Btuh/1000) Total Power in Kilowatts at
Temp. at Indicated Indoor Dry Bulb Temp. at Indicated Indoor Dry Bulb Temp.
1
Indicated Indoor Dry Bulb Temp.
F. 60 70 75 80 60 70 75 80 60 70 75 80
-8 17.2 16.9 16.8 16.6 15.5 15.2 15.1 14.9 3.78 4.11 4.30 4.51
-3 19.5 19.0 18.9 18.8 17.6 17.1 17.0 16.9 3.73 4.07 4.26 4.49
2 21.8 21.3 21.1 21.0 19.6 19.2 19.0 18.9 3.82 4.14 4.34 4.55
7 24.4 23.8 23.5 23.3 22.0 21.4 21.2 21.0 3.86 4.18 4.38 4.59
12 27.0 26.3 26.0 25.8 24.3 23.7 23.4 23.2 3.90 4.23 4.43 4.63
17 29.8 29.0 28.7 28.4 26.8 26.1 25.8 25.6 3.96 4.28 4.48 4.68
22 32.7 31.8 31.4 31.1 29.4 28.6 28.3 28.0 4.01 4.34 4.53 4.74
27 35.7 34.7 34.3 33.9 32.1 31.2 30.9 30.5 4.07 4.39 4.59 4.79
32 38.8 37.7 37.3 36.8 34.9 33.9 33.6 33.1 4.13 4.46 4.65 4.85
37 41.8 40.7 40.2 39.7 37.6 36.6 36.2 35.7 4.19 4.52 4.72 4.92
42 44.9 43.8 43.2 42.7 40.4 39.4 38.9 38.4 4.26 4.60 4.79 4.99
47 48.1 46.8 46.2 45.6 48.1 46.8 46.2 45.6 4.33 4.68 4.87 5.07
52 51.3 49.9 49.2 48.6 51.3 49.9 49.2 48.6 4.42 4.76 4.95 5.15
57 54.4 52.9 52.2 51.5 54.4 52.9 52.2 51.5 4.51 4.85 5.04 5.24
62 57.5 55.9 55.1 54.3 57.5 55.9 55.1 54.3 4.60 4.95 5.14 5.34
67 57.3 55.5 54.6 53.7 57.3 55.5 54.6 53.7 4.58 4.92 5.10 5.29
72 60.5 58.5 57.6 56.7 60.5 58.5 57.6 56.7 4.70 5.04 5.22 5.42
For other airflow conditions, see heating capacity correction factor (Table PD-39).
Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
Note:
1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.
Performance
Data (4 Ton)