Performance
Data (10 Ton)
Table PD-18 — Belt Drive Evaporator Fan Performance — 10-Ton — WSC120A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Field Supplied Low Static Drive (1)
3200 560 0.53 601 0.63 644 0.74 682 0.85 718 0.97 754 1.10 789 1.25 822 1.38 856 1.53 887 1.67
3600 620 0.73 657 0.83 694 0.95 731 1.08 764 1.20 797 1.33 829 1.48 860 1.63 892 1.79 922 1.95
4000 680 0.97 715 1.09 747 1.21 782 1.35 814 1.49 844 1.63 874 1.77 903 1.93 932 2.09 960 2.27
4400 741 1.27 773 1.40 803 1.53 834 1.67 864 1.82 894 1.98 922 2.13 948 2.28 975 2.44 1001 2.62
4800 803 1.62 833 1.76 861 1.90 887 2.04 916 2.20 972 2.55 997 2.71 1022 2.87 1046 3.04
2-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Table PD-18 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
3200 917 1.82 945 1.97 973 2.14 999 2.30 1024 2.47 1048 2.65 1072 2.82 1095 3.00 1117 3.17 1140 3.36
3600 951 2.11 979 2.27 1007 2.43 1033 2.60 1059 2.78 1082 2.95 1107 3.14 1130 3.33 1152 3.52 1173 3.71
4000 988 2.44 1015 2.62 1042 2.79 1068 2.97 1093 3.15 1117 3.33 1142 3.52 1164 3.70 1187 3.91 1209 4.11
4400 1028 2.81 1053 3.00 1078 3.19 1103 3.38 1128 3.57 1152 3.77 1176 3.96 1198 4.15 1221 4.36 1243 4.56
4800 1071 3.23 1095 3.42 1119 3.62 1142 3.83 1166 4.04 1189 4.25 1212 4.46 1233 4.66 1256 4.88 1277 5.09
5-HP Oversized Motor & Drive
Table PD-19— Belt Drive Evaporator Fan Performance — 10-Ton — WSC120A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2-HP Standard Motor & Drive
3200 656 0.81 691 0.89 730 1.00 771 1.13 807 1.26 844 1.39 886 1.55 926 1.72 965 1.89 1000 2.06
3600 729 1.13 761 1.22 792 1.32 829 1.45 865 1.60 898 1.74 930 1.89 965 2.06 1002 2.24 1038 2.43
4000 802 1.52 833 1.63 860 1.73 890 1.86 923 2.01 956 2.17 986 2.30 1015 2.48 1044 2.65 1077 2.85
4400 876 1.99 905 2.12 931 2.24 955 2.35 983 2.49 1014 2.66 1045 2.84 1072 3.01 1098 3.18 1125 3.36
4800 950 2.56 977 2.70 1002 2.84 1025 2.96 1048 3.08 1074 3.24 1102 3.43 1131 3.63 1156 3.81 1181 4.00
5-HP Oversized Motor & Drive
Table PD-19 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5-HP Oversized Motor & Drive
3200 1029 2.20 1057 2.35 1084 2.49 1108 2.63 1132 2.77 1155 2.91 1177 3.05 1198 3.18 1219 3.32 1239 3.46
3600 1072 2.62 1106 2.81 1134 2.98 1160 3.15 1185 3.31 1209 3.47 1231 3.63 1252 3.78 1274 3.94 1295 4.10
4000 1111 3.05 1143 3.26 1174 3.47 1204 3.68 1232 3.88 1260 4.09 1283 4.27 1306 4.46 1327 4.63 1349 4.81
4400 1152 3.55 1182 3.76 1211 3.99 1241 4.21 1270 4.44 1299 4.68 1327 4.91 1352 5.14 1377 5.37 1400 5.57
4800 1205 4.19 1229 4.39 1253 4.58 1280 4.81 1309 5.06 1336 5.31 1363 5.56
5-HP Oversized Motor& Field Supplied Sheave (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.00 x Fan BHP + .500.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VP34 x 7/8”, Fan Sheave AK69,and belt AX35 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
2-HP Standard Motor & Field Supplied Low Static Drive (1)
For Standard Evaporator Fan Speed (RPM), reference Table PD-20.
Notes:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 3.00 x Fan BHP + .500.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VP34 x 7/8”, Fan Sheave AK69, and belt AX35 required.
2. Field supplied Fan Sheave BK95 required.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.