General
Data (5, 6 Ton)
Table GD-2 — General Data
5 Ton Convertible Units 6 Ton Convertible Units
WSC060A1 WSC060A3,A4,AW WSC072A3,A4,AW
Cooling Performance
1
Gross Cooling Capacity 63,100 63,100 74,000
EER/SEER
2
— /9.70 — /10.10 10.6/ —
Nominal CFM / ARI Rated CFM 2,000/2,000 2,000/2,0000 2,400/2,100
ARI Net Cooling Capacity 60,000 60,000 70,000
Integrated Part Load Value
System Power (KW) 6.90 6.74 6.6
Heating Performance
1
High Temp. Btuh Rating 59,000 59,000 68,000
System Power KW/COP 5.96/ — 5.76/ — 6.04/3.3
Low Temp. Btuh Rating 36,200 36,200 38,000
System Power KW/COP 5.30/ — 5.05/ — 5.06/2.2
HSPF (Btu/Watts-hr) 6.96 7.00
Compressor
No./Type 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
3
85 85 90
Outdoor Coil — Type Lanced Lanced Lanced
Tube Size (in.) OD .3125 .3125 .3125
Face Area (sq ft) 9.59 9.59 17.00
Rows/FPI 3/17 3/17 2/17
Refrigerant Control Expansion Valve Expansion Valve Expansion Valve
Indoor Coil — Type Lanced Lanced Lanced
Tube Size (in.) .3125 .3125 .3125
Face Area (sq ft) 6.68 6.68 9.89
Rows/FPI 3/16 3/16 3/16
Refrigerant Control Short Orifice Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/¾ NPT 1/¾ NPT 1/¾ NPT
Outdoor Fan — Type Propeller Propeller Propeller
No. Used/Diameter (in.) 1/22 1/22 1/26
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1
CFM 3,200 3,200 6,200
No. Motors/HP 1/.40 1/.40 1/.70
Motor RPM 1,075 1,075 1,075
Direct Drive Indoor Fan — Type FC Centrifugal FC Centrifugal
No. Used 1 1
Diameter x Width (in.) 11 x 11
5
11 x 11
5
Drive Type/No. Speeds Direct/2 Direct/2
No. Motors 1 1
Motor HP (Standard/Oversized) .90/1.00 .90/1.00
Motor RPM (Low/High Speed) 985/1,100 985/1,100
Oversized Motor RPM (Low/High Speed) 1,080/1,135 1,080/1,135
Motor Frame Size (Standard/Oversized) 48/48 48/48
Belt Drive Indoor Fan — Type FC Centrifugal FC Centrifugal
No. Used 1 1
Diameter x Width (in.) 11 x 11 12 x 12
Drive Type/No. Speeds Belt/Variable Speed Belt/Variable Speed
No. Motors 1 1
Motor HP (Standard/Oversized) 1.00/ — 1.00/2.00
Motor RPM (Standard/Oversized) 1,750/ — 1,750/1,750
Motor Frame Size (Standard/Oversized) 56/ — 56/56
Filters — Type Furnished
6
Throwaway Throwaway Throwaway
(No.) Size Recommended (in.) (2) 20 x 25 x 1 (2) 20 x 25 x 1 (4) 16 x 25 x 2
Refrigerant Charge (Lbs of R-22)
4
7.9 8.5 8.2
Notes:
1. Cooling Performance and Heating Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb . Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification
program, which is based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-25.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5 Fan Diameter with oversized motor is 12 x 11.
6. Optional 2 inch pleated filters are also available.