Trane PKGP-PRC003-EN Heat Pump User Manual


 
PKGP-PRC003-EN
35
Table PD-39 —Electric Heater Voltage
Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal Distribution Capacity
Voltage Voltage Multiplier
208 0.751
240 230 0.918
240 1.000
440 0.840
480 460 0.918
480 1.000
540 0.810
600 575 0.918
600 1.000
Performance
Data
Table PD-38 — Auxiliary Electric Heat Capacity
Total
2
Stage 1 Stage 2
Unit KW MBh No. of KW MBh KW MBh
Tons Model No. Input
1
Output
1
Stages Input
1
Output
1
Input
1
Output
1
5.00 17.07 1 5.00 17.07
WSC036A1 10.00 34.14 2 5.00 17.07 5.00 17.07
13.80 47.11 2 8.80 30.04 5.00 17.07
3
6.00 20.48 1 6.00 20.48
WSC036A3, A4 12.00 40.97 2 6.00 20.48 6.00 20.48
17.40 59.40 2 8.70 29.70 8.70 29.70
5.00 17.07 1 5.00 17.07
4, 5 WSC048, 060A1 10.00 34.14 2 5.00 17.07 5.00 17.07
13.80 47.11 2 8.80 30.04 5.00 17.07
17.60 60.09 2 8.80 30.04 8.80 30.04
6.00 20.48 1 6.00 20.48
4 WSC048A3, A4, AW 12.00 40.97 2 6.00 20.48 6.00 20.48
17.40 59.40 2 8.70 29.70 8.70 29.70
6.00 20.48 1 6.00 20.48
5 WSC060A3, A4, AW 12.00 40.97 2 6.00 20.48 6.00 20.48
17.40 59.40 2 8.70 29.70 8.70 29.70
23.00 78.52 2 14.30 48.82 8.70 29.70
9.00 30.73 1 9.00 30.73
WSC072A3, A4, AW 18.00 61.45 1 18.00 61.45
6 27.00 92.18 2 18.00 61.45 9.00 30.73
36.00 122.90 2 18.00 61.45 18.00 61.45
9.00 30.73 1 9.00 30.73
WSC090A3, A4, AW 18.00 61.45 1 18.00 61.45
27.00 92.18 2 18.00 61.45 9.00 30.73
36.00 122.90 2 18.00 61.45 18.00 61.45
8.00 61.45 1 18.00 61.45
10 WSC120A3, A4, AW 27.00 92.18 2 18.00 61.45 9.00 30.73
36.00 122.90 2 18.00 61.45 18.00 61.45
54.00 184.36 2 36.00 122.90 18.00 61.45
Notes:
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =(
Voltage
)
2
x rated cap.
Rated Voltage