Electrical
Data
Table ED-1 — Unit Wiring
Standard Indoor Fan Motor Oversize Indoor Fan Motor Optional Belt Drive Indoor Fan Motor
3
Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size or Maximum Circuit Size or Maximum Circuit Size or Maximum
Tons Model No. Voltage Range
2
Ampacity Circuit Breaker
1
Ampacity Circuit Breaker
1
Ampacity Circuit Breaker
1
WSC036A1 187-253 26.2 40 28.6 45 N/A N/A
3 WSC036A3 187-253 19.1 30 21.5 30 21.8 30
WSC036A4 414-506 9.9 15 11.1 15 11.3 15
WSC036AW 517-633 8.3 15 8.9 15 8.9 15
WSC048A1 187-253 39.7 60 41.8 60 N/A N/A
WSC048A3 187-253 24.4 35 26.5 40 25.8 40
4 WSC048A4 414-506 12.1 15 13.7 20 12.9 20
WSC048AW 517-633 10.1 15 10.9 15 10.3 15
WSC060A1 187-253 48.7 60 50.4 60 N/A N/A
WSC060A3 187-253 32.6 50 34.3 50 31.4 50
5 WSC060A4 414-506 16.6 25 16.9 25 16.2 25
WSC060AW 517-633 13.1 20 13.7 20 12.7 20
WSC072A3 187-253 32.2 50 33.5 50
6 WSC072A4 414-506 16.6 25 17.2 25
WSC072AW 517-633 12.5 15 13.5 20
WSC090A3 187-253 41.4 60 45.8 60
WSC090A4 414-506 21.9 35 24.0 35
WSC090AW 517-633 16.8 25 18.8 25
WSC120A3 187-253 50.4 60 57.5 70
10 WSC120A4 414-506 26.4 35 29.9 35
WSC120AW 517-633 21.0 25 23.9 30
Notes:
1. HACR breaker per NEC.
2. Heater KW ratings are at 208-240volt for 208-230 volt units.
3. Optional Belt Drive motor applies to 3-5 ton models only.
The standard motor for 6-10 ton models is belt drive.