Trane CAB-PRC001-EN Electric Heater User Manual


 
Performance
Data
CAB-PRC001-EN22
Steam
Coils
Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure.
All performance measured on high speed tap, zero ESP, with a throwaway filter.
Table PD-7. Free Discharge Motor, Group 1
2 psig 5 psig
Unit CFM TMBH TMBH 115V 230V 277V
Size Coil (L/s) (TkW) Q/ITD (TkW) Q/ITD Watt Watt Watt
2 Steam 234 (110) 10.1 (2.9) 0.07 10.7 (3.1) 0.07 60 95 65
3 Steam 311 (147) 13.2 (3.9) 0.09 13.9 (4.1) 0.09 70 80 83
4 Steam 383 (181) 17.3 (5.1) 0.12 18.3 (5.4) 0.12 95 96 104
6 Steam 601 (284) 26.3 (7.7) 0.18 27.9 (8.2) 0.18 110 154 165
8 Steam 783 (370) 34.7 (10.2) 0.23 36.7 (10.8) 0.23 135 150 159
10 Steam 974 (460) 44.0 (12.9) 0.30 46.6 (13.7) 0.30 205 250 269
12 Steam 1104 (521) 51.1 (15.0) 0.34 54.2 (15.9) 0.35 230 246 263
Table PD-8. Free Discharge Motor, Group 2
2 psig 5 psig
Unit CFM TMBH TMBH 115V 230V 277V
Size Coil (L/s) (TkW) Q/ITD (TkW) Q/ITD Watt Watt Watt
2 Steam 207 (98) 9.6 (2.8) 0.07 10.1 (3.0) 0.07 60 95 65
3 Steam 277 (130) 12.5 (3.7) 0.08 13.3 (3.9) 0.08 70 80 83
4 Steam 346 (163) 16.6 (4.9) 0.11 17.6 (5.1) 0.11 95 96 104
6 Steam 538 (254) 25.1 (7.4) 0.17 26.6 (7.8) 0.17 110 154 165
8 Steam 702 (331) 33.1 (9.7) 0.22 35.1 (10.3) 0.22 135 150 159
10 Steam 875 (413) 42.1 (12.3) 0.28 44.6 (13.1) 0.28 205 250 269
12 Steam 993 (469) 48.9 (14.3) 0.33 51.8 (15.2) 0.33 230 246 263
Table PD-9. Free Discharge Motor, Group 3
2 psig 5 psig
Unit CFM TMBH TMBH 115V 230V 277V
size Coil (L/s) (TkW) Q/ITD (TkW) Q/ITD Watt Watt Watt
2 Steam 195 (92) 9.3 (2.7) 0.06 9.9 (2.9) 0.06 60 95 65
3 Steam 259 (122) 12.2 (3.6) 0.08 12.9 (3.8) 0.08 70 80 83
4 Steam 328 (155) 16.2 (4.7) 0.11 17.1 (5.0) 0.11 95 96 104
6 Steam 507 (239) 24.5 (7.2) 0.16 26.0 (7.6) 0.17 110 154 165
8 Steam 662 (312) 32.3 (9.5) 0.22 34.3 (10.0) 0.22 135 150 159
10 Steam 827 (390) 41.1 (12.0) 0.28 43.6 (12.8) 0.28 205 250 269
12 Steam 938 (443) 47.7 (14.0) 0.32 50.6 (14.8) 0.32 230 246 263
Note:
Q/ITD = MBH (kW)/(Saturated Steam temperature - Entering air temperature) when DT and GPM remain constant. To determine heating capacities at a different saturated steam or
entering air temperature, compute the new ITD and multiply it by the Q/ITD shown.