Trane CAB-PRC001-EN Electric Heater User Manual


 
Performance
Data
CAB-PRC001-EN 19
Hot Water
Coils
Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (-1 C)
T. All performance measured on high speed tap, zero ESP, and a throwaway filter.
Table PD-3. Free Discharge Motor, Group 2
Heating
Unit CFM TMBH GPM WPD 115V 230V 277V
Size Coil (L/s) (TkW) Q/ITD (L/s) (kPa) Watt Watt Watt
2 2H 211 (100) 14.5 (4.3) 0.13 0.97 (0.06) 4.1 (12.3) 60 95 65
3H 201 (95) 17.7 (5.2) 0.16 1.18 (0.07) 8.8 (26.2) 60 95 65
4H 188 (89) 18.3 (5.4) 0.17 1.22 (0.08) 2.4 (7.1) 60 95 65
3 2H 280 (132) 19.2 (5.6) 0.17 1.28 (0.08) 7.5 (22.4) 70 80 83
3H 277 (131) 23.3 (6.8) 0.21 1.55 (0.10) 3.2 (9.5) 85 89 101
4H 256 (121) 24.8 (7.3) 0.23 1.65 (0.10) 4.5 (13.4) 85 89 101
4 2H 349 (165) 23.8 (7.0) 0.22 1.58 (0.10) 2.8 (8.3) 95 96 104
3H 338 (159) 29.4 (8.6) 0.27 1.96 (0.12) 5.5 (16.5) 100 107 106
4H 320 (151) 31.7 (9.3) 0.29 2.11 (0.13) 7.9 (23.7) 100 107 106
6 2H 544 (257) 37.4 (11.0) 0.34 2.49 (0.16) 7.6 (22.8) 110 154 165
3H 541 (255) 45.4 (13.3) 0.41 3.03 (0.19) 3.6 (10.6) 125 130 124
4H 510 (241) 49.4 (14.5) 0.45 3.29 (0.21) 4.8 (14.5) 125 130 124
8 2H 706 (331) 47.0 (13.8) 0.43 3.13 (0.20) 3.4 (10.2) 135 150 159
3H 659 (311) 56.8 (16.7) 0.52 3.79 (0.24) 5.9 (17.8) 120 123 133
4H 627 (296) 61.8 (18.1) 0.56 4.12 (0.26) 8.1 (24.3) 120 123 133
10 2H 879 (415) 60.0 (17.6) 0.55 4.00 (0.25) 5.9 (17.7) 205 250 269
3H 886 (420) 76.4 (22.4) 0.69 5.09 (0.32) 11.4 (34.1) 225 237 230
4H 840 (397) 82.8 (24.3) 0.75 5.52 (0.35) 15.7 (46.8) 225 237 230
12 2H 996 (470) 69.4 (20.3) 0.63 4.62 (0.29) 8.3 (24.7) 230 246 263
3H 976 (461) 84.3 (24.8) 0.77 5.62 (0.35) 9.0 (26.8) 220 230 239
4H 921 (435) 91.8 (26.4) 0.83 6.12 (0.39) 10.2 (30.5) 220 230 239
Note:
1. CFM = Cubic feet per minute
2. TMBH = Total capacity (MBH)
3. GPM = Gallons per minute
4. WPD = Water pressure drop (feet of water)
5. Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when DT and GPM (L/s) remain constant. To determine heating capacities at a different entering water
temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
6. Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.
Table PD-2. Free Discharge Motor, Group 1
Heating
Unit CFM TMBH GPM WPD 115V 230V 277V
Size Coil (L/s) (TkW) Q/ITD (L/s) (kPa) Watt Watt Watt
2 2H 240 (113) 15.9 (4.7) 0.14 1.06 (0.07) 4.8 (14.4) 60 95 65
3H 230 ( 108) 19.6 (5.7) 0.18 1.31(0.08) 10.5 (31.4) 60 95 65
4H 210 (99) 20.1 (6.0) 0.18 1.34 (0.08) 2.8 (8.4) 60 95 65
3 2H 318 (150) 21.0 (6.2) 0.19 1.40 (0.09) 8.8 (26.3) 70 80 83
3H 314 (148) 25.6 (7.5) 0.23 1.70 (0.11) 3.8 (11.3) 85 89 101
4H 284 (134) 27.1 (7.9) 0.25 1.81 (0.11) 5.3 (15.7) 85 89 101
4 2H 388 (183) 25.6 (7.5) 0.23 1.71 (0.11) 3.2 (9.5) 95 96 104
3H 374 (177) 31.8 (9.3) 0.29 2.12 (0.13) 6.4 (19.0) 100 107 106
4H 350 (165) 34.2 (10.0) 0.31 2.28 (0.14) 9.1 (27.3) 100 107 106
6 2H 611 (289) 40.6 (11.9) 0.37 2.70 (0.17) 8.9 (26.5) 110 154 165
3H 608 (287) 49.7 (14.6) 0.45 3.31 (0.21) 4.2 (12.6) 125 130 124
4H 565 (267) 53.8 (15.8) 0.49 3.59 (0.23) 5.7 (17.0) 125 130 124
8 2H 790 (373) 50.9 (14.9) 0.46 3.39 (0.21) 4.0 (11.9) 135 150 159
3H 731 (345) 61.6 (18.1) 0.56 4.11 (0.26) 6.9 (20.7) 120 123 133
4H 688 (325) 66.8 (19.6) 0.61 4.45 (0.28) 9.4 (28.1) 120 123 133
10 2H 980 (463) 64.8 (19.0) 0.59 4.32 (0.27) 6.8 (20.4) 205 250 269
3H 992 (468) 83.3 (24.4) 0.76 5.55 (0.35) 13.4 (40.2) 225 237 230
4H 930 (439) 90.1 (26.4) 0.82 6.00 (0.38) 18.3 (54.8) 225 237 230
12 2H 1110 (524) 75.0 (22.0) 0.68 4.99 (0.32) 9.6 (28.6) 230 246 263
3H 1082 (511) 91.5 (26.8) 0.83 6.10 (0.38) 10.5 (31.4) 220 230 239
4H 1010 (477) 99.3 (28.5) 0.90 6.48 (0.42) 7.3 (21.8) 220 230 239