Trane CAB-PRC001-EN Electric Heater User Manual


 
General Data
CAB-PRC001-EN 13
Table GD-1. ForceFlo Cabinet Heater General Data
Unit Size 02 03 04 06 08 10 12
Coil Data
Face Area — Ft
2
(cm
2
) 0.8 (743) 0.8 (743) 1.1 (1020) 1.6 (1490) 2.1 (1950) 3.2 (2970) 3.2 (2970)
LxDxH — In. (cm)
2-Row 15x1.7x8 15x1.7x8 20x1.7x8 29.5x1.7x8 38x1.7x8 57x1.7x8 57x1.7x8
(38x4x20) (38x4x20) (51x4x20) (75x4x20) (97x4x20) (145x4x20) (145x4x20)
3-Row 15x2.6x8 15x2.6x8 20x2.6x8 29.5x2.6x8 38x2.6x8 57x2.6x8 57x2.6x8
(38x7x20) (38x7x20) (51x7x20) (75x7x20) (97x7x20) (145x7x20) (145x7x20)
4-Row 15x3.5x8 15x3.5x8 20x3.5x8 29.5x3.5x8 38x3.5x8 57x3.5x8 57x3.5x8
(38x9x20) (38x9x20) (51x9x20) (75x9x20) (97x9x20) (145x9x20) (145x9x20)
Volume — Gal. (Liters)
1-Row (Heat) .06 (.23) .06 (.23) .08 (.30) .11 (.42) .14 (.53) .21 (.79) .21 (.79)
2-Row .12 (.45) .12 (.45) .15 (.57) .22 (.83) .28 (1.06) .42 (1.59) .42 (1.59)
3-Row .18 (.68) .18 (.68) .23 (.87) .33 (1.25) .42 (1.59) .62 (2.35) .62 (2.35)
4-Row .24 (.91) .24 (.91) .30 (1.14) .44 (1.67) .56 (2.12) .83 (3.14) .83 (3.14)
Fins/Ft (cm)
2-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
3-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
4-Row 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7) 144 (4.7)
Fan/Motor Data
Fan Quantity 1 1 1 2 2 3 3
Size — Dia” x Width” (cm) 6.31x4 6.31x6.5 6.31x7.5 6.31x6.5 6.31x7.5 (1) 6.31x7.5 6.31x7.5
(16x10) (16x17) (16x19) (16x17) (16x19) (16x19) (16x19)
(2) 6.31x6.5
(16x6.5)
Motor Quantity 1 1 1 1 1 2 2
Filter Data
1 (cm) TA and Pl. Media
Quantity 1 1 1 1 1 1 1
Size — In. (cm) 8
7
/8 x 19
1
/8 8
7
/8 x 19
1
/8 8
7
/8 x 24
1
/8 8
7
/8 x 33
5
/8 8
7
/8 x 42
1
/8 8
7
/8 x 61
1
/8 8
7
/8 x 61
1
/8
(23x49) (23x49) (23x61) (23x85) (23x107) (23x155) (23x155)
1 Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity 1 1 1 1 1 1 1
Size — In. (cm) 5
1
/2 x 19
1
/8 5
1
/2 x 19
1
/8 5
1
/2 x 24
1
/8 5
1
/2 x 33
5
/8 5
1
/2 x 42
1
/8 5
1
/2 x 61
1
/8 5
1
/2 x 61
1
/8
(14 x 49) (14 x 49) (14 x 61) (14 x 85) (14 x 107) (14 x 156) (14 x 156)
Table GD-2. Cabinet Heater Air Flow
ESP
FD Motor High Static Motor
Unit Size Coil 0.05 0.1 0.2 0.3 0.4
2R144 240 330 300 280 250
02 3R144 230 330 300 270 240
4R144 200 300 270 250 220
2R144 320 410 390 350 320
03 3R144 310 400 360 330 290
4R144 280 370 340 300 270
2R144 390 450 410 380 340
04 3R144 370 550 510 470 430
4R144 340 510 480 440 400
2R144 610 760 700 650 590
06 3R144 610 890 830 770 710
4R144 560 820 760 710 660
2R144 800 1020 960 890 820
08 3R144 730 1000 930 870 800
4R144 680 940 870 810 750
2R144 980 1260 1180 1090 1010
10 3R144 1000 1400 1310 1210 1120
4R144 930 1300 1220 1130 1040
2R144 1110 1430 1330 1240 1140
12 3R144 1080 1520 1420 1330 1220
4R144 1000 1430 1340 1240 1150
Note: This is data is based on horizontal concealed model only, with duct inlet, duct outlet and no filter, dry coil, all voltages
except 208 V.