Toshiba RAV-SP240AT2-UL Air Conditioner User Manual


 
Toshiba
–4–
Outdoor Unit
Installation Manual
EN
3 SYSTEM REQUIREMENTS
Piping (Field supplied)
Minimum refrigerant line length between the outdoor
unit and indoor unit is 16.5” (5 m)
Maximum pipe lengths
Figure of Single
Refrigerant sizes
Flare nuts and flaring
The flare nuts and flaring are different from those for
the conventional refrigerant.
Use the flare nuts supplied with the air conditioner or
those for R410A.
Before performing flaring, carefully read
“REFRIGERANT PIPING”
Insulation
Both lines need to be insulated. Use a minimum 0.4”
(10 mm) wall thickness.
Refrigerant charge
* Caution during addition of refrigerant
Max. amount of additional refrigerant is 1.8 lbs (800
g).
Charge the refrigerant accurately. Overcharging
may cause serious trouble with the compressor.
* Minimum refrigerant pipe is 16’5”(5 m).
This may cause a malfunction of the compressor or
other devices.
Metering Device is an electronic EXV (PMV) in
outdoor unit.
Connecting power and control
cables (Field supplied)
The main power is supplied to the outdoor unit. The
field supplied connecting cables from the outdoor
unit to the indoor unit consist for 4 wires and provides
the power for the indoor unit as well as the
communication signal between the outdoor and
indoor unit.
System interconnection wire size must be AWG12.
Breaker must have a capacity specified in the
following table.
All wiring must comply with local electric codes and
NEC (National Electric Code) or CEC (Canadian
Electric Code).
Allowable
pipe length
(ft (m))
Height difference
(Indoor-outdoor H)
(ft (m))
Number of
bent portions
Total length
L
Indoor unit:
Upper
Outdoor unit:
Lower
10 or less
164’1” (50) 98’5” (30) 98’5” (30)
Liquid side Gas side
Outer
diameter
Thickness
Outer
diameter
Thickness
Ø3/8”
(9.5 mm)
0.03”
(0.8 mm)
Ø5/8”
(15.9 mm)
0.04”
(1.0 mm)
H
L
Indoor Unit
Outdoor Unit
Length of refrigerant
pipe connected to
indoor/outdoor unit
Additional refrigerant
16’5” - 98’5”
(5 - 30 m)
None
*98’5” - 164’1”
(30 - 50 m)
Add 0.43 oz/ft (40 g/m) of
refrigerant for piping that exceeds
98’5” (30 m) up to 164’1” (50 m).
Model RAV- SP240
Power supply 208/230 V, 60 Hz
MCA 24 A
MOCP (MAX Fuse/CB) 40 A
Breaker 25 A
System interconnection wires AWG12
MCA = Minimum Circuit Amps
MOCP =Maximum Over Protection Device Amps.
4-EN
+00EH99865401_00Ta.book Page 4 Wednesday, November 25, 2009 11:19 AM