Toshiba RAV-SM802KRT-E Air Conditioner User Manual


 
ON-SITE SETTING AND OTHERS (Continued)
Function Select Code (DN) Table
DN
01
02
03
06
OC
OF
10
11
12
13
14
1E
28
2A
2b
2E
31
32
60
69
8b
Item
Filter sign ON time
Filter contamination level
Central control address
HEAT intake temp. shift
PREPARING indication selection
COOL only
Type
Indoor unit capacity
Refrigerant line address
Indoor unit address
Group address
Temp. range at COOL/HEAT auto
switching control
Auto restart after power failure
Option/alarm input (CN80)
selection
Thermo output (T10-3) selection
HA terminal (T10-1) selection
Ventilation fan (single operation)
Sensor selection
Timer setting (wired R/C)
Flap setting for cooling
Correction of feeling of strong
heating
Description
0000: None 0001: 150H
0002: 2500H 0003: 5000H
0004: 10000H 0005: Clogging sensor used
0000: Average 0001: Heavy
(half of standard time)
0001: No. 1 - 0064: No. 64
0099: Not determined
0000: No shift 0001: +1 °C
0002: +2 °C - 0010: +10 °C
(Up to +6 recommended)
0000:
PREPARING indicated
0001: No indication
0000: Heat pump 0001: COOL only
(No “AUTO”, “HEAT”
indication)
0000: (Ceiling panel 1) 0001 (ceiling panel 4) -
0037
0000: Not determined 0001 - 0034
0001: No. 1 - 0030: No. 30
0001: No. 1 - 0064: No. 64
0000: Individual 0001: Group header
0002: Group follower
0000: 0deg - 0010: 10deg
(Switching at set temperature ±(data)/2)
0000: Not provided 0001: Provided
0000: Filter input 0001: Alarm input
0002:
External alarm input
0000:
I/U thermo sensor ON
0001: O/U compressor ON
output
0000: Normal (JEMA) 0001: Card input
0002: Fire alarm input
0000: Disabled 0001: Enabled
0000: Unit sensor TA 0001: R/C sensor
0000: Available 0001: Unavailable
0000: Normal 0001: Down allowed
0000: Not provided 0001: Provided
Factory setting
0001: 150H
0000: Average
0099: Not determined
0002: +2 °C
0000: PREPARING
indicated
0000: Heat pump
0008: Wall type
Depends on capacity
type
0099: Not determined
0099: Not determined
0099: Not determined
0033: 3deg (Ts ± 1.5)
0000: Not provided
0002: External alarm
input
0000: I/U thermo
sensor ON
0000: Normal
(HA terminal)
0000: Disabled
0000: Unit sensor
0000: Available
0000: Normal
0000: Not provided
57