NO.
11
Item
Flap control
Overview of specifications
(1) During the first operation after power on, flap position is controlled
automatically according to operation mode (COOL/HEAT).
(2) When louver position is controlled by remote controller, the unit’s
microcomputer memorizes the position for use in the next
operation.
* The memorized louver position is cleared when power is turned
off, and returns to the state of (1) above.
(3) Flap position setting
Flap position can be set within the range below.
COOL/DRY HEAT/FAN
Flap position can be set collectively or individually in the group
twin or triple operation mode. (Wireless remote controller allows
individual setting only.)
(4) Swing setting
Flap moves within the range below.
All operation modes
Flap swing range can be set collectively or individually in the
group twin or triple operation mode. (Setting by wireless remote
controller is disabled when the main remote controller is used.)
(5) When air conditioner operation stops, flap closes automatically. It
keeps its position in the event of an alarm.
(6) Flap tilts upward automatically during preparation for heating.
(7) In the twin or triple operation mode selected by wireless remote
controller, swing setting interlocks with the header indoor unit. If
this setting is transmitted from a follower indoor unit, operation
does not change with a reception sound “pi, pi, pi” if operation
mode differs between header unit and follower unit.
Remarks
Louver angle: 0 °C (full
close)
Alarm : A code number
(except F08 and
L31) appears on
the remote
controller and the
indoor unit stops.
Cooling Heating
103°
45°
Full close