– 8 –
3-2. RAV-SM800XT-E / RAV-SM800AT-E
Indoor unit
Outdoor unit
TCJ
sensor
Air heat exchanger
Strainer
Strainer
TC sensor
Refrigerant pipe
at liquid side
Outer dia. ∅B
Refrigerant pipe
at gas side
Outer dia. ∅A
Packed valve
Outer dia. ∅B
Packed valve
Outer dia. ∅A
Max
50m
TS sensor
Accumulator
(1500cc)
TD sensor
TO sensor
TE
sensor
4-way valve
(STF-0213Z)
∅25 x L160
Rotary compressor
(DA220A2F-20L)
Heat exchanger∅8
1 row 30 stages
FP1.3 flat fin
Modulating (PMV)
(SKV-18D26)
Capillary
∅3 x ∅2
x L530
∅25 x L210
Muffler
R410A 1.5 kg
Cooling
Heating
PsPd
Pressure Pipe surface temperature (°C)
(MPa) Discharge Suction
Indoor heat Outdoor heat Indoor
exchanger exchanger fan
Pd Ps (TD) (TS) (TC) (TE) Indoor Outdoor
Standard 3.3 0.9 89 8 8 40 64 HIGH 27/19 35/–
Cooling Overload 3.7 1.1 87 17 14 46 45 HIGH 32/24 43/–
Low load 1.0 0.8 22 2 1 1 24 LOW 18/15.5 –5/–
Standard 3.3 0.6 93 0 54 0 70 HIGH 20/– 7/6
Heating Overload 3.1 1.1 75 20 52 15 24 LOW 30.– 24/18
Low load 2.0 0.2 90 –26 25 –25 90 HIGH 0 –20/(70%)
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Compressor
revolutions
per second
(rps)
*
* 4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Outer diameter of refrigerant pipe
Gas side ∅A Liquid side ∅B
9.5 mm 15.9 mm