Toshiba RAV-SM1403DT-A Air Conditioner User Manual


 
– 54 –
Ta
(˚C)
-1.5
Tsc
Tsh
+1.5
Heating
(Cooling OFF)
(Cooling ON)
or
Cooling
No.
3
4
5
Item
Room temp.
control
Automatic
capacity control
(GA control)
Automatic
cooling/
heating control
Outline of specifications
1) Adjustment range: Remote controller setup temperature (°C)
Setting at shipment
Setup data 2
Setup data
Setup temp. correction
0246
+0°C+2°C+4°C+6°C
1) Based on the difference between Ta and Ts, the operation
frequency is instructed to the outdoor unit.
2) Cooling operation
Every 90 seconds, the room temperature difference
between temperature detected by Ta and Ts and the
varied room temperature value are calculated to obtain
the correction value of the frequency command and then
the present frequency command is corrected.
Ta (n) Ts (n) : Room temp. difference
n : Counts of detection
Ta (n-1) – Ts (n) : Varied room temp. value
n – 1:
Counts of detection of 90 seconds before
3) Heating operation
Every 1 minute (60 sec.), the room temperature differ-
ence between temperature detected by Ta and Ts and the
varied room temperature value are calculated to obtain
the correction value of the frequency command and then
the present frequency command is corrected.
Ts (n) Ta (n) : Room temp. difference
n : Counts of detection
Ta (n) Ta (n – 1): Varied room temp. value
n – 1 : Counts of detection of 1 minute before
1) The judgment of selecting COOL/HEAT is carried out as
shown below. When +1.5 exceeds against Tsh 10 minutes
and after thermo.-OFF, heating operation (Thermo. OFF)
exchanges to cooling operation. Description in the
parentheses shows an example of cooling ON/OFF.
When –1.5 lowers against Tsc 10 minutes and after thermo. OFF, cooling operation
(Thermo. OFF) exchanges to heating operation.
2) For the automatic capacity control after judgment of cooling/heating, see Item 4.
3) For temperature correction of room temp. control in automatic heating, see Item 3.
Remarks
Tsc: Setup temp. in
cooling operation
Tsh: Setup temp. in
heating operation
+ temp. correction of
room temp. control
2) Using the Item code 06, the setup temperature in heating
operation can be corrected.
Wired type
Wireless type
COOL
18 to 29
18 to 30
HEAT
18 to 29
16 to 30
AUTO
18 to 29
17 to 27
Shift of suction tempera-
ture in heating operation