Toshiba RAV-SM1403DT-A Air Conditioner User Manual


 
– 107 –
[P03 error]
[H01 error]
Check parts.
Defect Replace
Correct the cabling and
connection of connector.
Replace TD sensor.
Check and correct the
charged refrigerant amount.
Improve and
delete the cause
Check CDB.
Defect Replace
Improve power line.
Improve and delete the cause.
Check IPDU.
Defect Replace
Is power voltage normal?
Is not abnormal overload?
Is not abnormal overload?
Is charged refrigerant
amount normal?
Are connections of
cable/connector normal?
Is protective control
such as discharge temprelease
control normal?
Are characteristics
of TD sensor resistance
value normal?
NO
NO
NO
NO
NO NO
NO
YES
YES
YES
YES
YES
YES
YES
Refer to 10-2-6. Relational graph of temperature sensor
resistance value and temperature Characteristics-4.